18
RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
Product Description
Components
•
Fire Alarm - red indicator
•
Supervisory - yellow indicator
•
AC Power - green indicator
•
System Trouble - yellow indicator
•
Alarm Silenced - yellow indicator
•
Discharge - red indicator
•
Pre-discharge - red indicator
•
Abort - yellow indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervi-
sory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse ½ second on and ½ second off
•
Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring inter-
face connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are the optional dress panel DP-51050
[red] and trim-ring TR-CE [red]. The Canadian version is supplied standard with a modified dress
panel and one N-ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the NFS-LBB or BB-26). Batteries must be ordered separately.
1.5 Optional Modules and Accessories
N-CAC-5X Class A Converter Module
The N-CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required
to convert all six Initiating Device Circuits and four Output Circuits.
4XTM Transmitter Module
The 4XTM provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm condi-
tion exists. The 4XTM mounts to the main circuit board connectors J4 & J5.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for
Canadian applications requiring remote annunciation.
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...