RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
55
Master Programming Level
Programming
Pressing the down arrow key displays additional zone types as indicated in the following table.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Manual Release
1
1 Activation of a Manual Release Switch will override Predischarge Delay and override
an active Abort Release Switch, resulting in an immediate agent release.
Fire Alarm
Manual Release/Abort
Fire Alarm
Discharge Pressure
2
2 Discharge Pressure Switch can be mapped to one or both Release Circuits,
but it will
not activate them
. The following will occur when it is avtivated:
Alarm LED flashes 1/2 second on, 1/2 second off
Discharge LED turns on steady
Alarm Relay(s) activate
Momentarily activate/energize any relay programmed as a pre-discharge relay
Activate any relay programmed as a discharge relay
Turn on all enabled and mapped NACs
Display an active IDC message on FACP display and send message to printer/pc
Turn on FACP piezo
Fire Alarm
Normally Open Contact
Fire
N/A
N/A
N/A
Waterflow
Fire
Waterflow NS (nonsilenceable)
Fire, nonsilenceable
Combo
Fire/Supervisory
Combo w/AutoResettable Superv
3
3
AutoResettable
means that a device with this type code, when activated, will automat-
ically reset when the corresponding condition is cleared.
Fire/Supervisory, nonlatching
2-Wire Smoke
Fire Alarm
2-Wire Heat
Fire Alarm
N/A
Linear Heat
Fire Alarm
N/A
N/A
Fire
Fire Alarm
Low Pressure
Supervisory, latching
Low Pressure AutoResettable
Supervisory, nonlatching
High Pressure
Supervisory
High Pressure AutoResettable
Supervisory, nonlatching
Disable Release
4
4
Disable Release
allows the installer to disable the releasing solenoids during system
testing. Disable Release will only work when the system is
not
in alarm.
Supervisory, nonlatching (disables Release Circuits)
Supervisory
Supervisory, latching
Supervisory AutoResettable
Supervisory, nonlatching
Abort Release Switch
5
5 Activation of an Abort Release Switch during system normal operation (non-alarm)
results in an audible and visual indication at the FACP. If the Abort Switch is pressed
and then the Manual Release is activated, the Manual Release will over-ride the Abort
and cause an immediate release. If Manual Release is activated and then Abort
Switch is pressed, the Abort Switch will have no effect.
Supervisory, nonlatching
N/A
Table 3.1 Zone Types