RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
71
Master Programming Level
Programming
In the technical information screen, pressing
1
for
Type
will display the following screens:
Press the number corresponding to the module type, if any, that is installed with the selected
address.
This will enable the module
.
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online. The software will search for all ANN-BUS modules and automatically
program the device type and address into the system. Pressing
3
while viewing ANN-BUS Screen
#1 will begin the Auto-Configure process and cause the following screen to be displayed:
ANN-S/PG Options
The Printer Option allows the user to configure the optional printer. Pressing
1
while viewing the
ANN-BUS Screen #2 will display the following screens:
Pressing
1
for Port while viewing Printer Options screen #1 will allow the programmer to select
between a Parallel and Serial Port for printer connection. Each press of the
1
key will cause the
display to toggle between
Port PAR
(parallel) and
Port SER
(serial). It is important to note that the
interface selected determines which options are available to the user.
If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing
2
for Printer Supervision while viewing Print Options
screen #1. Each press of the
2
key will cause the display to toggle between
Printer Supv NO
for no
supervision and
Printer Supv YES
for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.
If the Parallel Port option is selected, the user has the ability to select an
Offline Timer
by pressing
3
while viewing Print Options screen #1. The resultant screen allows the programmer to program
the
Offline Timer
for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.
If the Serial Port option is selected, the
Printer Supv
and
Offline Timer
options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.
Pressing
1
for
Baud Rate
while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of
19200, 9600, or 2400
.
Pressing
2
for
Data Bits
while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select
5, 6, 7,
or
8 Data Bits
.
NOTE:
When the Secondary ANN-BUS is enabled through System Setup programming, addresses
1 - 3 will be on the primary ANN-BUS and addresses 4 - 8 will be on the seconary ANN-BUS.
ANN-BUS MODULE TYPE
1=NONE
2=ANN-80
3=ANN-I/O
Module Type Screen #1
ANN-BUS MODULE TYPE
1=ANN-S/PG
2=ANN-RLY
3=ANN-LED
Module Type Screen #2
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen
PROGRAMMING
1=ANN-S/PG OPTIONS
2=ANN-I/O OPTIONS
3=ANN-80 OPTIONS
ANN-BUS Screen #2
ANN-S/PG OPTIONS
1=PORT PARALLEL
2=PRINTER SUPV NO
3=OFFLINE TIMER 60
Printer Options Screen #1
ANN-S/PG OPTIONS
1=BAUD RATE N/A
2=DATA BITS N/A
3=PARITY N/A
Printer Options Screen #2
ANN-S/PG OPTIONS
1=STOP BITS N/A
Printer Options Screen #3
Summary of Contents for NOTIFIER RP-2002C