RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
87
Walktest
Operating Instructions
4.14 Walktest
Walktest is a feature which allows one person to test the fire alarm system. An audible walktest will
momentarily sound the Notification Appliance Circuits in the building and store the walktest infor-
mation in a file at the panel. A silent walktest will not sound the NACs but will store the walktest
information in a file which can be viewed at the panel. Disabled NAC devices will not activate
during walktest. In addition,
i
3
smoke detectors will enter their own test mode causing their LEDs
to flash twice every five seconds (refer to
i
3
specification document).
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed con-
trol outputs for four seconds, for
any
mapped NAC (silenceable or non-silenceable activation). It
also stores each alarm in the walktest history file which can be sent to an optional printer. The
stored display will be the same as if the device actually activated except the colon (
:
) in the time
stamp is replaced with an asterisk (
*
).
Open Condition
Initiating Device Circuits as well as all main circuit board NACs are monitored for fault conditions
during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs pro-
grammed for Walktest, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble indicator flashes (as in all
of the Program and status change operations). The alarm relay is not activated.
4.15 Read Status
Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm or trouble occurs during these functions, the Read Status is exited to pre-
vent confusion.
Read Status Entry
When the operator presses the control panel
Enter
key, the LCD will display the following:
Pressing
1
, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus mode which allows the user to view and print the programmed features and status of the control
panel.
The following screens will be displayed:
1=READ STATUS MODE
2=PROGRAMMING MODE
READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #1
Read Status Screen #3
READ STATUS
1=TIMERS
2=DAYLIGHT SAVINGS
3=HISTORY
Read Status Screen #2
READ STATUS
1=PRINT
2=ANN-BUS
Read Status Screen #4
Summary of Contents for NOTIFIER RP-2002C
Page 158: ...Cut along dotted line ...