UDACT-2 — Instruction Manual
P/N 54089:B3 10/29/2019
27
Report
Programming
Function: Defaults to Fire Alarm. From the pull-down menu, select the point/zone type that matches the FACP’s point type.
Point/zone type selections are:
Point Address at Central Station: When an ACS point is selected in this tab, this field displays the point address number that will display
on a report to the Central Station. It is read-only.
For the NFS2-3030, NFS-3030, NCA-2, NCA, AM2020 and AFP1010 the first eight points to be monitored by the Central Station are
reserved for system trouble messages from the panel, and can not be programmed. Figure 3.5 above shows that the first eight addresses -
A1P1 through A1P8 - are reserved for the panel. If the ACS addresses to be monitored had started with A2, A2P1 through A2P8 would
be reserved for system trouble messages. These addresses do not generate a point address to the Central Station. A1P9 will display at the
Central Station as Point Address 1.
For the NFS2-640 and NFS-320, point reporting is displayed below. Note that Loop 2 reporting is only available for the NFS2-640.
Loop 1, Modules 1 - 64 report as device numbers 001 - 064
Loop 2, Modules 1 - 64 report as device numbers 065 - 128
Loop 1, Modules 65 - 128 report as device numbers 129 - 192
Loop 2, Modules 65 - 128 report as device numbers 193 - 256
Loop 1, Modules 129 - 159 report as device numbers 257 - 287 (288 is not used)
Loop 2, Modules 129 - 159 report as device numbers 289 - 319 (320 is not used)
Loop 1, Detectors 1 - 64 report as device numbers 321 - 384
Loop 2, Detectors 1 - 64 report as device numbers 385 - 448
Loop 1, Detectors 65 - 128 report as device numbers 449 - 512
Loop 2, Detectors 65 - 128 report as device numbers 513 - 576
Loop 1, Detectors 129 - 159 report as device numbers 577 - 607 (608 is not used)
Loop 2, Detectors 129 - 159 report as device numbers 609 - 639 (640 is not used)
3.6 Report
A printed report with point or zone information can be generated from VeriFire Tools for an ONYX Series panel or network annunciator.
In the UDACT-2 programming service, select UDACT-2 from the dropdown Reports Menu on the top menu bar.
The point report consists of the central station point address; ACS point, ACS point function; panel label; panel point; type code; custom
and extended label; alarm verification and walktest participation; and presignal and PAS information. This report may be sent to the Cen-
tral Station for their records.
The zone report consists of a grid with the central station point address; ACS point address; source; ACS point function; custom label;
and panel label.
• Fire Alarm
• Water Flow
• 24 Hour Non-Burglary • Pump Failure
• Disabled
• Duct Detector
• High Temperature
• Photo/CO detect
• Supervisory
• Pre-alarm
• Lower Temperature
• Pull Station
• Smoke
• Low Water Pressure
• Heat Detector
• Burglary
• Low Water Level
!
CAUTION:
BE SURE THE CORRECT POINT TYPE IS ENTERED. IF THERE IS A MISMATCH BETWEEN THE UDACT-2’S POINT
TYPE AND THE FACP OR NETWORK ANNUNCIATOR’S POINT TYPE, THE UDACT-2 WILL TRANSMIT A FIRE
ALARM MESSAGE TO THE CENTRAL STATION WHEN THAT POINT ACTIVATES.
NOTE:
Programming for the panel or network annunciator and the UDACT-2 must be contained in the same database for this
report to generate.