NPB-2X-RS485 OPTION CARD
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
95-7778—01 M.S. 08-10
Printed in U.S.A.
WEB/CP-202/602-XPR Controller
The WEB/CP-202/602-XPR series controller accepts only one
(1) option card, where ports for the NPB-2X-RS485 are COM7
and COM8.
WEB/CP-201/600/700 and SEC-H-201/600
Controllers
For the controller models WEB/CP-201/600/700 and
SEC-H-201/600) up to two RS-485 option cards may be
installed, where:
•
If a
single
RS-485 option is in Option Slot 1, the ports are
COM3, COM4.
•
If there are
two
RS-485 options, the ports are COM3,
COM4 for Option Slot 1, and COM5, COM6 for Option Slot
2.
•
If a
single
NPB-2X-RS485 option card is in Option Slot 2,
the ports are COM3, COM4, unless one of the following
cards are in Option Slot 1:
•
If an NPB-2X-RS485 option card is in slot 1, then the
ports for slot 2 are COM5, COM6.
•
If an NPB-GPRS option card is in slot 1, then the ports
for slot 2 are COM4, COM5.
• If a WEB/CP-700 controller and installed in Option Slot 1,
or if the only option card, ports are COM5 and COM6.
If the option card is installed in Slot 1 of a controller along with
another option card that uses COM ports in Option Slot 2,
note that COM assignments for that other card are affected:
• For example, if a WEB/CP-201/600 with an
NPB-2X-RS485 option installed in Slot 1, and a single port
RS-232 option (NPB-RS232) installed in Slot 2, COM
assignments are: Slot 1 (RS-485): COM3, COM4, Slot 2
(RS-232): COM5.
• The same option card mix in a WEB/CP-700 controller
yields: Slot 1 (RS-485): COM5, COM6, Slot 2 (RS-232):
COM7
• The NPB-2X-RS485 installed in the only (single) option slot
of a WEB/CP-202/602 controller is seen as COM7 and
COM8.
Table 2. COM Port Assignments Based on Controller and Option Card Configuration.
Controller Model
Slots Used
Card Slot 1
Card Slot 2
1st Option Card
COM Ports
2nd Option Card
COM Ports
SEC-H-201/600
1 only
NPB-2X-RS485
COM3 COM4
Not Used (Empty)
1 and 2
Not Used (Empty)
NPB-2X-RS485
COM3 COM4
1 and 2
NPB-2X-RS485
COM3 COM4
NPB-2X-RS485
COM5 COM6
1 and 2
NPB-GPRS
COM3
NPB-2X-RS485
COM4 COM5
WEB/CP-201/600
1 only
NPB-2X-RS485
COM3 COM4
Not Used (Empty)
2 only
Not Used (Empty)
NPB-2X-RS485
COM3 COM4
1 and 2
NPB-2X-RS485
COM3 COM4
NPB-RS232
COM5
1 and 2
NPB-2X-RS485
COM3 COM4
NPB-2X-RS485
COM5 COM6
1 and 2
NPB-GPRS‘
COM3
NPB-2X-RS485
COM4 COM5
WEB/CP-700
1 only
NPB-2X-RS485
COM5 COM6
Not Used (Empty)
1 and 2
NPB-2X-RS485
COM5 COM6
NPB-RS232
COM7
1 and 2
NPB-2X-RS485
COM5 COM6
NPB-2X-RS485
COM7 COM8
WEB/CP-202/602-XPR
1 only
NPB-2X-RS485
COM7 COM8
There is no second card slot.
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the
literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including
attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.