Installation Overview
Multinode/WSG installation
28
OneWireless Multinode User's Guide
R110
6/08
Step
Action
1
Examine the lightning arrestors and remove and discard the following items
(if not needed).
Securing nut, washer and ring terminal (but retain the screw).
2
Attach the 10, 12, and 18-inch wires to the appropriate lightning arrestor body
ensuring that the smaller (#8) ring terminals and those wires with identifying
labels are used.
3
Secure the ring terminal to the lightning arrestor using a screwdriver.
4
Install the two lightning arrestors to the multinode by attaching one end of the
lightning arrestor to the multinode's MESH and AP connectors.
Make sure that the lightning arrestor with the 12-inch wire is mounted closer
to the ground stud and that the lightning arrestor with the 18-inch wire is
mounted on the antenna connector farther from the ground stud.
5
Secure the lightning arrestors to the Type N connectors so that they are hand
tight. Do not over tighten.
6
Install the Type N lightning arrestor with the 10-inch wire to the multinode by
attaching one end of the lightning arrestor to the multinode's Type N FIELD
I/O (or FHSS) ANTENNA connector. Hand tighten only.
Note: Steps 7 and 8 may need to be performed once the multinode is
mounted and connected at its site location.
7
Construct a grounding wire to be used for the earth ground connection. See
Grounding
in the next section for additional information.
Attach the ground wire to the ring terminal attached to the multinode’s
grounding stud.
The earth ground ring terminal must be the first connection on the multinode's
grounding stud when making additional connections to the grounding stud.
8
Place the ring terminals from the lightning arrestor ground cables on the
grounding stud of the multinode enclosure and secure with a screw.
Note that the earth ground ring terminal should be attached to the multinode
before the lightning arrestor's ring terminal is attached.
It is recommended that the outdoor protection kit be replaced every three years. If the
unit is operated in an area subject to intense lightning activity, it is recommended that the
outdoor protection kit be replaced every year.
Summary of Contents for OW-CDX050
Page 1: ...OneWireless Multinode User s Guide OW CDX050 R110 6 08 ...
Page 24: ...Agency compliance information R TTE Directive 12 OneWireless Multinode User s Guide R110 6 08 ...
Page 82: ...Configuration System Administration 70 OneWireless Multinode User s Guide R110 6 08 ...
Page 134: ...Honeywell International Process Solutions 2500 West Union Hills Phoenix AZ 85027 ...