Installation Overview
Multinode/WSG installation
30
OneWireless Multinode User's Guide
R110
6/08
ATTENTION
The power cable attached to the multinode may be one of the following:
•
Red cable with two wires (Red and Black)
•
Grey cable with two wire pairs (Red and Green, Black and White)
The red (or grey) power cable, the Green/yellow grounding cable and Ethernet cables are
connected as follows:
Step
Action
1
Ensure that all power is removed from the power cabling run to the multinode
site.
2
If the multinode is equipped with a Red power cable:
•
Connect the Red wire from the multinode power cable to +24 volt dc output
of the power supply in the junction box.
•
Connect the Black wire from the multinode power cable to the 24 volt
COMMON of the power supply.
If the multinode is equipped with a Grey power cable:
•
Connect both the Red and Green wires from the multinode power cable to
+24 volt dc output of the power supply in the junction box.
•
Connect both the Black and White wires from the multinode power cable to
the 24 volt COMMON of the power supply.
3
Cut and tie back the drain wire from the power cable.
4
Connect the Green/Yellow grounding cable from the multinode to a safety
ground point.
5
The two WAN cables, labeled WLAN1 and WLAN2 (Ethernet cables), from
the multinode are configured with the same IP address and a single MAC
address and should be regarded as a two-port Ethernet switch. Therefore, if
the control system provides connections to redundant switches, then use
both Ethernet cables to connect to the separate switches.
If only a single switch available in the control system, then use WLAN1
Ethernet cable to connect to the network switch. The two Ethernet cables
should not be connected to the same network switch.
Note: Using the WLAN1 cable enables the the WLAN LED indicator.
Summary of Contents for OW-CDX050
Page 1: ...OneWireless Multinode User s Guide OW CDX050 R110 6 08 ...
Page 24: ...Agency compliance information R TTE Directive 12 OneWireless Multinode User s Guide R110 6 08 ...
Page 82: ...Configuration System Administration 70 OneWireless Multinode User s Guide R110 6 08 ...
Page 134: ...Honeywell International Process Solutions 2500 West Union Hills Phoenix AZ 85027 ...