background image

P520 SIGNAL PROCESSOR

66-2066—01

10

TROUBLESHOOTING

Module Communications

The P520 communicates with any host computer that has a 

USB port and supports ASCII character code transmission at 

4800 baud (or, in current revisions of the processor chip, at 

4800 or 9600 baud). The baud rate is displayed with the 

module address in the current versions (see SETTING 

ADDRESSES, section). The data transmitted to and from the 

P520 is over two twisted pairs that are differentially driven and 

received according to the RS-422 standard. The differential 

mode allows long wire runs in harsh, electrical environments. 

Honeywell offers a RS485/422 to USB converter to use in 

conjunction with the P520 signal processor. The Honeywell 

part number is COMMOD.

Modbus Communication protocol allows the P520 to 

communicate with open process controllers or human-

interface host computers that support this protocol. The P520 

processor status and settings are organized as 23 4X holding 

registers and five 0X discrete registers. For more information 

on Modbus protocol, please refer to Modicon’s Modbus 

Protocol Reference Guide (PI-MBUS-300 Rev E).

Communication Setting

P520 can communicate only in Modbus RTU mode, with the 

following configuration:

• 9600 baud

• 8 data bits

• No parity

• 1 stop bit

The factory default of a P520 station number is 0. It is 

important to change the station number so that there are no 

duplicate stations in the network. 

Table 5. Troubleshooting procedures.

Problem

Troubleshooting Steps

No flame signal and no display.

1.

Check the wiring between the signal processor and the viewing 

head. Refer to the Wiring the Rear PC Board section.

2.

Using a volt meter check the voltage at PWR IN terminals with a 

volt meter. It should measure approximately 24VDC. If not, 

check the power supply and wiring, or replace the power supply.

3.

If 24VDC is measured, remove the power for 10 seconds. If the 

self-resetting fuse has tripped, removing then reapplying power 

will reset the fuse.

Digital display shows 0000 and there is no flame signal.

1.

Remove connector from viewing head and check wiring per 

Fig. 4 and 5.

2.

Ensure the proper impedance resistor is in place (refer to Wiring 

of Viewing Head section). Using a volt meter, check the viewing 

head terminals on the P520, for 24VDC V and GND. If 

the voltage is low, check input voltage to the signal processor. If 

the input voltage is measured to be in spec, remove power and 

disconnect all connections to the viewing head(s). Wait 10 sec-

onds (which resets the self-resetting fuse) and then reapply 

power and re-measure voltage V and GND.

3.

If voltage me24VDC (nominal) at the viewing head ter-

minals at the signal processor, turn off power to the signal pro-

cessor and using an ohmmeter check continuity of each cable 

wire from the signal processor terminals to the viewing head 

connector terminals. If cable continuity checks out, the viewing 

head may be defective.

Flame signal shows on display; flame on relay and light 

are off.

1.

The viewing head is incorrectly wired, or defective (see above).

2.

The set point values for flame ON are incorrect.

Flame signal shows on analog bar graph display; flame 

light is off; lockout light is on.

1.

The viewing head may be defective.

2.

There may be a noise or grounding problem. Check that equip-

ment is properly grounded and ensure good clean contact on all 

ground connections. Move viewing head and cable/conduit at 

least 12 inches (31 cm) away from any source of high powered 

switching (e.g. igniter equipment). Refer to Grounding and 

Shielding section.

3.

Press the RESET button on the front panel.

The 1-9 LED stays on.

1.

There may be a noise or grounding problem (see above and 

refer to Grounding and Shielding section).).

2.

The viewing head may be defective.

The front panel buttons do not respond.

1.

The P520 front panel may be locked out.

2.

Signal processor may be in remote operation only mode.

3.

Cycle power to the signal processor with the viewing head con-

nected.

Summary of Contents for P520

Page 1: ... each Viewing Head Battery Backup 24VDC 130mA plus 100mA for each Viewing Head Main Voltage Battery Voltage Ambient Temperature 0 C to 52 C 32 F to 125 F CSA Rating 0 C to 60 C 32 F to 140 F FM Rating Outputs Flame Relay 2 Form C Contacts DPDT Self Checking Relay 1 Form C Contact SPDT Contact Ratings 5A at 30 VDC 125 VAC and 277 VAC Max switching voltage 220Vdc 250Vac Analog Flame Signal 0 to 19 8...

Page 2: ...ard control technician 4 After installation is complete check out product opera tion as provided in these instructions Grounding and Shielding NOTE Installer must be a trained experienced flame safeguard service technician and should be familiar with the equipment operation and limita tions and be aware of any applicable local codes and regulations 1 Connect a safety ground to the viewing head hou...

Page 3: ...e located on the nine contact terminal block located on the upper right of the board RC C refers to the common terminal of the self checking relay There is only one pair of contacts used for the self checking function Here the designation ON refers to the self checking taking place in a normal manner OFF indicates a failure in the viewing head or processor resulting from the internal or external h...

Page 4: ...The voltage developed across the resistor will follow Ohm s law V IR For example a 3 volt meter can be used with a resistor of 3 02 150 ohms which will result in a full scale reading of 3 volts for a 20mA output The terminals called TX TX RX and RX at the bottom of the PCB are used for the serial communication link They are also in pairs to accommodate daisy chaining but the pairs are arranged for...

Page 5: ...en SC and SIG GND terminals for proper signal trans mission For resistor value refer to Wiring of Viewing Head section Fig 4 Viewing head wiring Table 1 Terminal Descriptions Terminal Description V 24VDC power to viewing head GND Power Ground SC Self check shutter drive signal to viewing head SIG Flame signal from viewing head SIG GND Signal ground M33509 CABLE CLAMP CONNECTOR WITH REAR COVER REMO...

Page 6: ... fuses are re set when power to the signal processor is removed It is recommended that no more than four P520 signal processors be supported by one 24VDC power supply unless a method of redundancy is employed together with larger capacity power supplies Other possible combinations can be used for instance the battery backup terminal could be used for redundancy However care must be taken with thes...

Page 7: ... P520 There is a 20 per cent probability that a lockout will occur because of the duty cycle of the self check function 200 mSEC on and 800 mSEC off The S506 and S511 do not incorporate the power monitoring shutdown function and will not cause a lockout condition These design precautions ensure that there will never be an unsafe situation created by abnormal line power 115VAC conditions The 26VDC ...

Page 8: ...akes for the flame relay to de energize after the flame signal from the viewing head is below the programmed Flame Off setpoint This time delay is programmable from both the front panel of the P520 and a remote host computer Only three settings are possible one two and three seconds The maximum time delay is limited to three seconds in compliance with the FM Factory Mutual limit of the F F R T to ...

Page 9: ...e maximum signal Adjusting Set Points Before adjusting the set points take readings with the P520 on the two following conditions write down the readings for the burner ON and OFF with other burners on under low load conditions and then the readings for the burner ON and OFF under high load conditions There must be a definitive ratio between the readings for burner ON and burner OFF This ratio can...

Page 10: ...onds If the self resetting fuse has tripped removing then reapplying power will reset the fuse Digital display shows 0000 and there is no flame signal 1 Remove connector from viewing head and check wiring per Fig 4 and 5 2 Ensure the proper impedance resistor is in place refer to Wiring of Viewing Head section Using a volt meter check the viewing head terminals on the P520 for 24VDC across V and G...

Page 11: ... must have galvanic ground isolation Setting Addresses Each P520 must have its own unique address The address can easily be changed by pressing the RESET push button for 2 seconds This causes the P520 to display its address on the four digit display 0000 to 0063 The address can now be changed by using the UP or DOWN arrow buttons When the desired address is displayed push the STORE button and the ...

Page 12: ... USE SHIELDED CABLE FOR COMMUNICATION WIRING DRAWING IS FOR GENERAL REFERENCE ONLY FOR RS422 COMMUNICATION WITH THE P520 4 WIRES FROM EACH SIGNAL PROCESSOR WILL BE REQUIRED RX RX TX TX FOLLOWING POLARITY FROM EACH SIGNAL PROCESSOR AT THE CONVERTER THE TRANSMIT AND RECEIVE WIRES WILL BE REVERSED REFER TO FIG 7 FOR CONVERTER TO SIGNAL PROCESSOR WIRING DETAILS COMMOD USB TO RS422 485 CONVERTER M33904...

Page 13: ... IR Y AUNN ADJUST UV GAIN 0 99 Y NORMAL OPERATION N Y N DISCARD CHANGES NORMAL OPERATION Y KEEP NEW FILTER SELECTION ARFN ADJUST IR FILTER 1 8 Y KEEP NEW UV GAIN ANNN ADJUST IR GAIN 0 699 N DISCARD CHANGES Y Y N DISCARD CHANGES Y KEEP NEW IR GAIN N Y SET DEFAULT VALUES ADJ ADJUST VIEWING HEAD SETTINGS DEF RESET TO FACTORY DEFAULT CALR AUTO ADJUST IR GAIN PROGRAMMING FLOWCHART FOR P520 WITH S550B B...

Page 14: ...Y CALIBRATE IR Y Y NORMAL OPERATION N NORMAL OPERATION Y KEEP NEW FILTER SELECTION ARFN ADJUST IR FILTER 1 8 ANNN ADJUST IR GAIN 0 699 N DISCARD CHANGES Y Y N DISCARD CHANGES Y KEEP NEW IR GAIN N Y SET DEFAULT VALUES ADJ ADJUST VIEWING HEAD SETTINGS DEF RESET TO FACTORY DEFAULT CALR AUTO ADJUST IR GAIN PROGRAMMING FLOWCHART FOR P520 WITH S552B BE M33290A ...

Page 15: ...ATE VIEWING HEAD N N CALU AUTO ADJUST UV GAIN NORMAL OPERATION CALIBRATE UV Y Y AUNN ADJUST UV GAIN 0 99 Y NORMAL OPERATION PROGRAMMING FLOWCHART FOR P520 WITH S556B BE Y N DISCARD CHANGES NORMAL OPERATION Y KEEP NEW UV GAIN N Y SET DEFAULT VALUES ADJ ADJUST VIEWING HEAD SETTINGS DEF RESET TO FACTORY DEFAULT N M33291A ...

Page 16: ...tion and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2012 Honeywell International Inc 66 2066 01 M S 10 12 Printed in United States ...

Reviews: