If the set temperature difference E03 is negative, an alarm is given
if it is too cold in the refrigerated area,
e.g. E03 = –10 K, cold store setpoint = –18 °C
➝
alarm at –28 °C in refrigerated area.
If the set temperature difference E03 is positive, the alarm is given
if it is too warm in the refrigerated area,
e.g. E03 = +10 K, cold store setpoint value = –18 °C
➝
alarm at –8 °C in the refrigerated area.
Attention: any change of the cold store setpoint valve changes also
the alarm temperature.
If E03 is set to 0, no alarm will be given.
PCR-300RC only:
E2’1 1st defrost time
––– (none), 00.1 to 23.5 hours
––– (none)
E2’2 2st defrost time
––– (none), 00.1 to 23.5 hours
01’0 hours
E2’3 3st defrost time
––– (none), 00.1 to 23.5 hours
07’0 hours
E2’4 4st defrost time
––– (none), 00.1 to 23.5 hours
13’0 hours
E2’5 5st defrost time
––– (none), 00.1 to 23.5 hours
19’0 hours
E2’6 6st defrost time
––– (none), 00.1 to 23.5 hours
––– (none)
The time is entered in increments
of 10 minutes in each case.
Caution: The times must be entered
in ascending order.
Exiting programming mode: Press the
key after the last level has
been entered.
6.6 Setting the time (PCR-300RC only)
I
Press and hold down the
and
keys at the same time for
approx. 5 seconds to access the first programming level
(Display: E00).
I
Setting: Press and hold down the
key and change
the time to the current time using the
or
key
(increments of 10 minutes).
Display
Setting range
Preset
E00 Time
00.0 to 23.5 hours
12’0 hours
Exiting programming mode:
Press the
key several times.
12