4.

Determine the pressure point at which minimum 

modulation output will occur by checking the boiler 

pressure gauge and subtracting the modulation range 

knob setting (at midpoint).

5.

Turn the modulation setpoint knob slowly 

counterclockwise and make sure the firing rate motor 

continues to move to the closed position. Make sure the 

firing rate motor reaches the lowfire position when the 

modulation setpoint reaches the pressure point 

identified in step 

4

 above. (Alternately, make sure the 

measured current decreases gradually toward 4 mA.)

Check the limit setpoint as follows (boiler pressure required):

1.

Turn the control setpoint knob clockwise until the control 

circuit closes. Make sure the yellow LED is flashing and 

the green LED is on, indicating normal operation with a 

call for heat.

2.

Turn the limit setpoint knob slowly counterclockwise and 

make sure that the P7810 opens the circuit and indi-

cates a safety lockout by alternately flashing the yellow 

and green LED (see LED Display section) when the limit 

setpoint passes through the boiler pressure gauge 

value.

3.

Make sure that the Alarm output is energized.

Check for normal system operation as follows:

1.

Set all knobs to the required operating position.

2.

Press the reset button to clear the safety lockout 

condition.

3.

Start the system and observe the operation through at 

least one complete cycle to make sure the P7810 

functions properly as described in the Operation 

section.

TROUBLESHOOTING

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

Line voltage is present at the P7810 and in all 

controller circuits. Use extreme care when 

troubleshooting.

To determine control malfunctions, use checkout procedures 

as listed in the Checkout section.

CAUTION

Equipment Damage Hazard.

Can cause equipment damage or improper 

operation.

Do not put the system into service until you have 

satisfactorily completed all applicable tests described 

in this checkout section, and also all tests in the 

Checkout section of the applicable instructions for the 

primary safety control and any other tests the burner 

and boiler manufacturer require.

SERVICE INFORMATION

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.

1

. Only qualified Flame Safeguard technicians should 

attempt to service Flame Safeguard controls and 

burners.

2

. Line voltage is present in the electrical circuits to the 

P7810 Pressuretrol® Controller. Open the master 

electrical switch before replacing the device. More 

than one power supply disconnect may be involved.

Scheduled Inspection and Maintenance

Calibration

The P7810 Pressuretrol® Controller was carefully calibrated 

during manufacturing and does not require field calibration.

Maintenance

Keep the cover of the P7810 Pressuretrol® Controller in place 

at all times to protect the internal components from dust, dirt 

and physical damage. Routine maintenance consists of 

occasional inspection and removal of accumulated dirt and 

dust. Make sure the P7810 Pressuretrol® Controller is 

functioning properly by performing an operation check of the 

entire system during routine maintenance checks.

Summary of Contents for Pressuretrol P7810A

Page 1: ...rode the pressure sensing element Models available with on off control function on off control and modulate high limit and modulate and on off control and safety high limit functions Models available in 15 150 and 300 psi 103 1034 and 2069 kPa maximum setpoints LED indicators show power call for heat function and lockout status Clear cover allows setpoint and differential to be read but not adjust...

Page 2: ...ntact Ratings a P7810C D models only Sensor Material 304 stainless steel Pressure Connector P7810A B 1 4 in NPT P7810C D 1 2 in NPT Case Material Plastic Electrical Terminations Screw terminals Accuracy 4 0 percent full scale output operating range over operating temperature Environmental Ratings Operating Temperature Range 32 F to 140 F 0 C to 60 C Storage Temperature Range 20 F to 150 F 29 C to ...

Page 3: ...fore removing old control 3 Follow all installation and checkout procedures for safe installation IMPORTANT Do not remove the overpressure inlet seal until ready to connect piping to prevent contamination of inlet Location Install the P7810 Pressuretrol Controller above the boiler water line when used with steam boilers Connect the siphon loop part number 14026 for P7810A B 209731A for P7810C D or...

Page 4: ...with an approved weather tight enclosure CAUTION Equipment Damage Hazard Incorrect installation of the L404 Pressure Controller can damage the equipment and may require boiler replacement Install the L404C Pressuretrol as shown in Fig 2 and 3 to prevent equipment damage Fig 2 Connecting P7810A B Pressuretrol Controller to steam boiler Fig 3 Right and wrong mounting of steam trap siphon loop for th...

Page 5: ...onnect may be involved All wiring must comply with applicable electrical codes ordinances and regulations Use NEC Class 1 line voltage wiring For normal installation use moisture resistant No 14 wire maximum size allowed suitable for at least 167 F 75 C or 194 F 90 C for Flame Safeguard Primary Controls Use shielded wire for 4 to 20 mA modulating output and terminate the shield to earth ground Do ...

Page 6: ...1 2 12 13 15 14 R B W 4 TO 20mA ALARM FIELD WIRING 2K1 1K1 DEVICE WIRING OUTPUT 3K1 14 LOW FIRE 15 MODULATE 13 COMMON 8K1 8K2 9K2 9K1 AUTO MAN 66 5 OHM 237 OHM 12 HIGH FIRE 7800 SERIES PROGRAMMER W M20568C R B MODUTROL IV MOTOR CONTROLLER P7810 4 2O mA SERIES 90 1K OHM 7800 SERIES SHOWN REFER TO SPECIFICATIONS PACKED WITH THE PROGRAMMER FOR WIRING OF OTHER PRIMARY SAFETY CONTROLLERS 1 1 LOW FIRE 1...

Page 7: ...ferential setting This cycle continues until power is removed opening the relay See Fig 11 Fig 11 P7810 on off control function versus pressure Modulate Control Function P7810B C Only When the pressure decreases to or below the modulation setpoint the current is 20 mA The current remains constant at all pressures below the modulation setpoint The modulation range is an additive value to the modula...

Page 8: ...ed Stop Limit Value P7810C D CAUTION Equipment Damage Hazard Exceeding pressure vessel limits can damage equipment The Maximum Fixed Stop Limit pressure setting must not exceed the maximum working pressure rating of the pressure vessel Adjust the Maximum Fixed Stop Limit setting to maximum working pressure rating that is stamped on the pressure vessel by the manufacturer IMPORTANT The Maximum Fixe...

Page 9: ...g fault code until the reset switch is released Both LEDs turn on after three seconds indicating the Maximum Fixed Stop Limit Value has been stored Wait for up to 30 seconds for a release Enter lockout after 30 seconds The green LED turns off and the yellow LED turns on waiting until the reset switch is released Both LEDs turn on Wait for up to 30 seconds for a release Lockout after 30 seconds If ...

Page 10: ...te Control P7810B C Only The P7810B C adds 4 to 20 mA modulation output and uses two additional potentiometers The pressure sensor output is fed to an error and gain amplifier to perform the modulation determined by the control potentiometer settings The potentiometer knobs mounted on the P7810B C face adjust the current output for a given set of pressures The modulation range is an additive value...

Page 11: ...form these tests the boiler pressure should be near the middle of the P7810 pressure range 2 Turn the P7810 limit setpoint knob fully clockwise to make sure this limit does not interfere during steps 4 and 5 This setting must return to the proper operating position when returning the system to normal operation 3 Check the control setpoint and control differential 4 Set the control differential kno...

Page 12: ...obs to the required operating position 2 Press the reset button to clear the safety lockout condition 3 Start the system and observe the operation through at least one complete cycle to make sure the P7810 functions properly as described in the Operation section TROUBLESHOOTING WARNING Electrical Shock Hazard Can cause severe injury death or property damage Line voltage is present at the P7810 and...