background image

PRODUCT DATA

® U.S. Registered Trademark
Copyright © 1998 Honeywell Inc.   •   All Rights Reserved

P7810C,D

Pressuretrol

®

 Controller

APPLICATION

The P7810 Pressuretrol® Controller is a line voltage pressure
controller that provides automatic operating control, automatic
safety high limit protection, and optional modulating firing rate
control for pressure systems up to 300 psi.

FEATURES

Use only with steam, air or noncombustible gases that
do not corrode the pressure sensing element.

Models available with on-off control function, safety
high limit and modulate, and on-off control and safety
high limit functions.

Models available in 15, 150, and 300 psi maximum
setpoints.

LED indicators show power and call for heat function
and lockout status.

Clear cover allows setpoint and differentials to be
read, but not adjusted, without opening cover.

Manual reset possible without opening cover.

P7810C contains on/off Control, High Limit and
4 to 20 mA Firing Rate Control.

P7810D contains on/off Control and High Limit
Control.

Contents

Application ........................................................................... 1
Features .............................................................................. 1
Specifications ......................................................................

2

Ordering Information ...........................................................

2

Installation ........................................................................... 3
Operation ............................................................................

4

Checkout and Troubleshooting ............................................

7

Troubleshooting ...................................................................

8

Service Information .............................................................

8

65-0235-1

Summary of Contents for Pressuretrol P7810C

Page 1: ...th on off control function safety high limit and modulate and on off control and safety high limit functions Models available in 15 150 and 300 psi maximum setpoints LED indicators show power and call for heat function and lockout status Clear cover allows setpoint and differentials to be read but not adjusted without opening cover Manual reset possible without opening cover P7810C contains on off...

Page 2: ... safety high limit P7810D Pressuretrol Controller with on off control and safety high limit Electrical Ratings Power Input 120 Vac 10 15 50 60 Hz Power Consumption Sensor Material 304 stainless steel Case Material Plastic Electrical Terminations Screw terminals Operating Temperature Range 32 F to 150 F 0 C to 65 C StorageTemperature 20 F to 150 F 29 C to 65 C Accuracy 4 0 percent full scale output...

Page 3: ...t scale and corrosive vapors from attacking controller sensor element Mount the siphon loop in any position with a 0 to 90 pipe drain position Mount the P7810C D Pressuretrol Controller next to the pressure gauge in the manufacturer provided fitting on the boiler See Fig 2 Mount at a remote location to avoid excessive vibration or mount in a special mounting on a low water cutoff IMPORTANT 1 Locat...

Page 4: ...ed 3 Pitch the piping properly to drain the condensate back to the boiler 4 Mount the siphon loop between the remote piping and the P7810C D Pressuretrol Controller 5 Level the P7810C D Pressuretrol Controller after the installation WIRING WARNING Electrical Shock Hazard Can cause electrical shock serious injury or death Disconnect the power supply before wiring More than one power supply disconne...

Page 5: ...g rate to steam pressure changes b Steam pressure safety high limit control causes a safety shutdown and lockout when the steam pressure reaches a preset safety high limit setpoint Fig 5 Firing Rate Wiring Diagram using P7810C D Pressuretrol Controller and Series 90 Modutrol Motor with Manual Position Potentiometer and Auto Manual Switch M11892A 7800 SERIES PROGRAMMER MODUTROL MOTOR P7810 PRESSURE...

Page 6: ...ses to or below the modulation setpoint the current is 20 mA The current remains constant at all pressures below the modulation setpoint The modulation range is an additive value to the modulation setpoint value When the pressure increases above the modulation setpoint the current decreases linearly until the modulation range point is reached The output current is 4 mA at and above this pressure S...

Page 7: ...s carefully calibrated at the factory Test the P7810 Pressuretrol Controller as follows NOTE Make sure the P7810 is operating properly by checking the LED indicators If the P7810 LED indicate a lockout condition press the manual reset button NOTE This procedure simulates pressure changes using dial setpoint adjustments Make dial adjustments very slowly because of filtering delays within the P7810C...

Page 8: ...ety lockout condition 3 Start the system and observe the operation through at least one complete cycle to make sure the P7810 functions properly as described in the Operation section TROUBLESHOOTING WARNING Electrical Shock Hazard Can cause electrical shock serious injury or death Line voltage is present at the P7810 and in all controller circuits Use extreme care while troubleshooting To determin...