Installation Instructions for the
Heavy Duty Pressure Transducers
PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi
32313758
Issue B
General Information
Honeywell’s PX3 Series Pressure Transducers use piezoresistive
sensing technology with ASIC (Application Specific Integrated
Circuit) signal conditioning in a brass housing and Metri-Pack
150 electrical connector. The PX3 Series are fully calibrated and
temperature compensated from -40 °C to 125 °C [-40 °F to
257 °F].
Safety and Productivity Solutions
Table 1. Electrical Specifications
Characteristic
Parameter
Supply voltage:
5 Vdc
3.3 Vdc
±0.25 Vdc
±0.25 Vdc
Over voltage and reverse voltage
±16 Vdc
Current consumption:
5 Vdc supply
3.3 Vdc supply
3.0 mA max.
1.6 mA to 2.1 mA
Short circuit protection
yes
Nominal output transfer function:
5 Vdc supply
3.3 Vdc supply
0.5 Vdc to 4.5 Vdc (ratiometric to supply)
0.33 Vdc to 2.97 Vdc (ratiometric to supply)
Table 2. Performance Specifications (At 25 °C [77 °F] and under unless otherwise noted.)
Characteristic
Parameter
Operating temperature range
1
-40 °C to 125 °C [-40 °F to 257 °F]
Storage temperature range
1
-40 °C to 125 °C [-40 °F to 257 °F]
Compensated temperature range
-40 °C to 125 °C [-40 °F to 257 °F]
Total Error Band
2
:
-20 °C to 85 °C [-4 °F to 185 °F]
<-20 °C, >85 °C [<-4 °F, >185 °F]
±1.0 %FSS
±2.0 %FSS
Accuracy BFSL
3
±0.25 %FSS
Response time
<2 ms (10% to 90% step change in pressure)
Turn on time
4
<7 ms
EMC rating
5
:
surge immunity (all leads)
electrostatic discharge
radiated immunity
fast transient burst
immunity to conducted disturbances
radiated emissions
radiated immunity
±1000 V line to ground per IEC 61000-4-5
±4 kV contact, ±8 kV air per IEC 61000-4-2
10 V/m (80 MHz to 1000 MHz) per IEC 61000-4-3
±1 kV per IEC 61000-4-4
3 V per IEC 61000-4-6
40 dB (30 MHz to 230 MHz), 47 dB (230 MHz to 1000 MHz) per CISPR 11
200 V/m per ISO 11452-2
Insulation resistance
>100 MOhm, 1500 Vdc
Dielectric strength
AC1500V, 1 min. or AC1800V, 1 s
Load resistance
>5 kOhm
Life
greater than 10 million full scale pressure cycles over the calibrated pressure range
1
Dependent on external and internal seal and cable jacket materials. See Table 5 and Figure 5 for temperature range details.
2
Total Error Band: The maximum deviation from the ideal transfer function over the entire compensated temperature and pressure range. In-
cludes all errors due to offset, full scale span, pressure non-linearity, pressure hysteresis, pressure non-repeatability, thermal effect on offset,
thermal effect on span, and thermal hysteresis. See Figure 1.
3
Accuracy: The maximum deviation in output from a Best Fit Straight Line (BFSL) fitted to the output measured over the pressure range at
25 °C [77 °F]. Includes all errors due to pressure non-linearity, pressure hysteresis, and pressure non-repeatability. See Figure 1.
4
Turn on Time: Duration from power applied until first valid output.
5
Tested using 1,5 m [59.1 in] cable.