Installation Instructions for the

Heavy Duty Pressure Transducers
PX3 Series, 1 bar to 50 bar | 15 psi to 700 psi

32313758

Issue B

General Information

Honeywell’s PX3 Series Pressure Transducers use piezoresistive 
sensing technology with ASIC (Application Specific Integrated 
Circuit) signal conditioning in a brass housing and Metri-Pack 

150 electrical connector. The PX3 Series are fully calibrated and 
temperature compensated from -40 °C to 125 °C [-40 °F to 
257 °F]. 

Safety and Productivity Solutions

Table 1. Electrical Specifications

Characteristic

Parameter

Supply voltage:
   5 Vdc
   3.3 Vdc

±0.25 Vdc 
±0.25 Vdc

Over voltage and reverse voltage

±16 Vdc

Current consumption:
   5 Vdc supply
   3.3 Vdc supply

3.0 mA max. 
1.6 mA to 2.1 mA

Short circuit protection

yes

Nominal output transfer function:
   5 Vdc supply
   3.3 Vdc supply

0.5 Vdc to 4.5 Vdc (ratiometric to supply)
0.33 Vdc to 2.97 Vdc (ratiometric to supply)

Table 2. Performance Specifications (At 25 °C [77 °F] and under unless otherwise noted.)

Characteristic

Parameter

Operating temperature range

1

-40 °C to 125 °C [-40 °F to 257 °F]

Storage temperature range

1

-40 °C to 125 °C [-40 °F to 257 °F]

Compensated temperature range

-40 °C to 125 °C [-40 °F to 257 °F]

Total Error Band

2

:

   -20 °C to 85 °C [-4 °F to 185 °F]
   <-20 °C, >85 °C [<-4 °F, >185 °F]

±1.0 %FSS
±2.0 %FSS

Accuracy BFSL

3

±0.25 %FSS

Response time

<2 ms (10% to 90% step change in pressure)

Turn on time

4

<7 ms

EMC rating

5

:

   surge immunity (all leads)
   electrostatic discharge
   radiated immunity
   fast transient burst
   immunity to conducted disturbances
   radiated emissions
   radiated immunity

±1000 V line to ground per IEC 61000-4-5
±4 kV contact, ±8 kV air per IEC 61000-4-2
10 V/m (80 MHz to 1000 MHz) per IEC 61000-4-3
±1 kV per IEC 61000-4-4
3 V per IEC 61000-4-6
40 dB (30 MHz to 230 MHz), 47 dB (230 MHz to 1000 MHz) per CISPR 11
200 V/m per ISO 11452-2

Insulation resistance

>100 MOhm, 1500 Vdc

Dielectric strength

AC1500V, 1 min. or AC1800V, 1 s

Load resistance

>5 kOhm

Life

greater than 10 million full scale pressure cycles over the calibrated pressure range

1

 Dependent on external and internal seal and cable jacket materials. See Table 5 and Figure 5 for temperature range details.

2

 Total Error Band: The maximum deviation from the ideal transfer function over the entire compensated temperature and pressure range. In-

cludes all errors due to offset, full scale span, pressure non-linearity, pressure hysteresis, pressure non-repeatability, thermal effect on offset, 

thermal effect on span, and thermal hysteresis. See Figure 1.

3

 Accuracy: The maximum deviation in output from a Best Fit Straight Line (BFSL) fitted to the output measured over the pressure range at 

25 °C [77 °F]. Includes all errors due to pressure non-linearity, pressure hysteresis, and pressure non-repeatability. See Figure 1.

4

 Turn on Time: Duration from power applied until first valid output.

Tested using 1,5 m [59.1 in] cable.

Summary of Contents for PX3 Series

Page 1: ...tep change in pressure Turn on time4 7 ms EMC rating5 surge immunity all leads electrostatic discharge radiated immunity fast transient burst immunity to conducted disturbances radiated emissions radiated immunity 1000 V line to ground per IEC 61000 4 5 4 kV contact 8 kV air per IEC 61000 4 2 10 V m 80 MHz to 1000 MHz per IEC 61000 4 3 1 kV per IEC 61000 4 4 3 V per IEC 61000 4 6 40 dB 30 MHz to 2...

Page 2: ...t zero pressure in order to mini mize measurement error over temperature The output is calibrated to be proportional to the difference between applied pressure and a reference of 1 standard atmosphere 1 013 barA 14 7 psiA Example 100 psi sealed gage has a calibrated pressure range from 14 7 psi absolute to 114 7 psi absolute 1 Sealed gage option only available in pressure ranges at or above 8 bar ...

Page 3: ... to 257 F 1 Honeywell can assist with selecting suitable seal material for the media based on the seal manufacturer s recommendation The customer should test the compatibility with the media to ensure that it is correct for the application CAUTION PRODUCT DAMAGE Ensure torque specifications are determined for the specific application Values provided are for reference only Mating materials and thre...

Page 4: ...ail Diagnostics Mode The PX3 Series diagnostics mode allows the device to indicate when internal or external faults occur If an internal fault occurs the output will rail to the preset lower or upper limit values shown in Figure 3 and Table 6 External faults will result in the sensor s output exceeding those preset limits lower or upper For example if the external sensor ground signal were lost th...

Page 5: ...e turns from finger tight Weight 35 1 g 1 2 oz N2 1 8 27 NPT Seal Pipe thread Mating geometry ANSI B1 20 1 Installation torque Two to three turns from finger tight Weight 31 2 g 1 1 oz T1 Tube Seal Brazing Weight 32 g 1 1 oz ø17 0 0 67 ø21 60 0 85 ø15 9 0 63 12 2 0 48 15 4 0 61 37 4 1 47 49 6 1 95 7 16 20 UNF 1 4 in 45 Flare Female Schrader SAE J512 35 9 1 41 13 9 0 55 11 2 0 44 1 85 47 1 ø17 0 0 ...

Page 6: ...ree turns from finger tight Weight 70 g 2 5 oz N2 1 8 27 NPT Seal Pipe thread Mating geometry ANSI B1 20 1 Installation torque Two to three turns from finger tight Weight 66 g 2 3 oz T1 Tube Seal Brazing Weight 67 g 2 4 oz ø21 6 0 85 1000 50 39 9 1 9 13 9 0 55 11 2 0 44 31 6 1 24 42 75 1 683 G1 4 A G ISO 1179 3 44 1 1 73 13 5 0 53 ø21 6 0 85 30 6 1 20 12 9 0 51 1000 50 39 9 1 9 M12 x 1 5 ISO 6149 ...

Page 7: ...Honeywell be liable for consequential special or indirect damages While Honeywell may provide application assistance personally through our literature and the Honeywell web site it is buyer s sole responsibility to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of this writing...

Reviews: