Q7751A ROUTERS
3
95-7510—3
Table 1. Router Wiring Connections.
Screw Terminal
Wiring Connection
1 and 2
Incoming network wiring, polarity insensitive; CHANNEL A.
3 and 4
Outgoing network wiring, polarity-insensitive; CHANNEL A.
5 and 14
Cable shields; terminals 5 and 14 are internally connected.
6 and 7
Incoming power wiring 16 to 30 Vac or Vdc at 2.0 VA, polarity-insensitive. If using dc power, maintain
continuity of the power polarity throughout the network. Terminals 6 and 8 should be the same polarity.
Terminals 7 and 9 should be the same polarity.
10 and 12
Unused
Jumpered together internally; can be used to land extra wires.
11 and 13
Jumpered together internally; can be used to land extra wires.
15 and 16
Incoming network wiring, polarity insensitive; CHANNEL B.
17 and 18
Outgoing network wiring, polarity-insensitive; CHANNEL B.
Table 2. Router Specifications.
Function Description
Processor
Two Echelon Neuron
®
3150 chips. 10 Mhz.
Service function
Recessed service switch, service LED. Dual tear-off bar code Neuron
®
ID self-adhesive tag for application
to redline drawings in the field.
Transceiver type
Depends on model. FTT-10 for Q7751A2010
TP-78 for Q7751A1012
Network connector
Ten orange screw terminals, non-removable, wire clamp style. Supports 12 to 24 AWG (4 to 0.27 mm
2
)
wire, shielded or unshielded daisy-chained cable. Two phone plug connectors are front panel accessible;
one per channel.
Input power
16 to 30 Vac or Vdc at 2.0 VA, internally isolated power supply.
Power connector
Four black screw terminals, non-removable, wire clamp style. Supports 12 to 24 AWG (4 to 0.27 mm
2
)
daisy-chained wire.
Mounting
Use with suitable back plate. Electrical box type or wall/35 mm DIN type.
Temperature
-40 to +185
o
F (-40 to +85
o
C) operating and non-operating.
Humidity
10 to 95% RH at 122
o
F (50
o
C).
EMI
FCC A, CE Mark
Safety agency
UL 916
INSTALLING THE ROUTER
Install the router using the following steps:
1.
Make sure the Type 2 base plate is correctly wired,
installed, and fastened to the electrical enclosure.
2.
Check for continuity on all network and power wiring.
3.
Make sure all network channels are terminated with
the correct number and type of terminator. Either one
or two terminator(s) can be installed in unused screw
terminals at the end of a network run.
4.
Insert the router into the Type 2 base plate.
a.
Align the network access jacks on the router
with the arrowhead on the Type 2 base plate
(the arrow should point toward the jacks).
b.
Firmly press router into the base plate to make
sure the module is properly seated in its base
plate connector.
NOTE: The router can be hot plugged. There is no
need to disconnect power when installing
the module. If power is present, the Power
LED lights. If power is not present, the
Power LED is off.
5.
Screw the two 8-32 x 3/8 in, (9.5 mm) screws into the
threaded inserts in the base plate.
6.
Configure the router as described in the appropriate
software user guide.
7.
See Troubleshooting section if necessary.