background image

R7195A,B MOTOR POSITIONER

63-2582

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Home and Building Control Sales Office (check white pages of your phone directory).

2.

Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

SPECIFICATIONS

Models:

See Table 1.

Table 1. R7195A,B Models.

Operating Temperature Range:

-30°F to +150°F (-35°C to +66°C).

Slidewire Resistance:

135 ohms or 1000 ohms.

Input Range—R7195A (4-20 mA):

Adjustments: 

Zero: 0.8 to 16.8 mA.

Span: 2.0 to 20.0 mA.

Deadband: 1% to 5%.

Factory Settings:

Zero: 4.0 mA input = 0% to 5% feedback potentiometer 

position.

Full Scale: 20 mA = 95% to 100% feedback potentiometer 

position.

Input Range—R7195B (135-ohm retransmitting slidewire 

input):

Adjustments:

Zero: 0% to 80% of slidewire input.

Span: 12.5% to 125% of slidewire input.

Deadband: 1% to 5% of slidewire input.

Factory Settings:

Zero: 0% to 2% input potentiometer = 0% to 10% feedback 

potentiometer position.

Full Scale: 98% input potentiometer = 90% to 100% 

feedback potentiometer position.

Repositions:

1% Deadband Setting = 100 repositions.

5% Deadband Setting =   20 repositions.

Input Impedance:

R7195A: 75 ohms.

R7195B: 1 Megohm.

Dimensions:

See Fig. 1.

Weight:

R7195A: 2.7 lbs (1.2 kg).

R7195B: 3 lbs (1.4 kg).

Approvals:

Underwriters Laboratories, Inc. Listed: Type 4 Enclosure, File 

Number 84572.

CSA Certified: Enclosure 4, File Number LR47125.

Model Number Operating Voltage

Controller Input

R7195A1031

120 Vac, 60 Hz

4-20 mA

R7195A1056

120 Vac, 60 Hz

4-20 mA (equipped for 

1000-ohm feedback 

slidewire)

R7195A1064

220 Vac, 60 Hz

4-20 mA

R7195B1021

120 Vac, 60 Hz

135-ohm input

Summary of Contents for R7195A

Page 1: ...ctionator Heavy duty case Mounts directly on M940 Actuator Solid state design extends product life and reliability Zero span and deadband adjustments allow motor to be field adjusted to various input ranges i e split ranging Hard Manual feature allows operator to override the controller 4 20 mA or 135 ohm input action to open or close fully the final control element Reversing direction of motor ca...

Page 2: ...o 66 C Slidewire Resistance 135 ohms or 1000 ohms Input Range R7195A 4 20 mA Adjustments Zero 0 8 to 16 8 mA Span 2 0 to 20 0 mA Deadband 1 to 5 Factory Settings Zero 4 0 mA input 0 to 5 feedback potentiometer position Full Scale 20 mA 95 to 100 feedback potentiometer position Input Range R7195B 135 ohm retransmitting slidewire input Adjustments Zero 0 to 80 of slidewire input Span 12 5 to 125 of ...

Page 3: ...Refer to Fig 1 and layout of the centers of the mounting hole locations on the mounting surface 1 Use a center punch and hammer to mark the locations for drilling 2 Depending on the characteristics of the mounting surface drill clearance holes No 23 bit for No 6 machine screws or starting holes No 37 bit for No 6 self tapping screws 3 Place the positioner on the surface so that the mounting holes ...

Page 4: ...tentiometer Fig 3 Multiple R7195B Motor Positioners connected to one 135 ohm input potentiometer Wiring Motor Positioner to Motor Terminals 1 Refer to wiring diagrams and documentation supplied with the motor to connect the motor positioner for specific applications 2 To avoid inductive interference to the internal circuitry separate the leads carrying line voltage from all other leads 3 Provide c...

Page 5: ... G L2 L1 2 3 1 B W R G 3 2 1 6 5 4 GROUND NEUTRAL HOT R7195 SUPPLY M940A MOTOR TERMINALS TO 4 20 mA INPUT B W R CW 135 OHM POTENTIOMETER INPUT M20790 R7195A B MOTOR POSITIONER 5 4 6 G L2 L1 2 3 1 B W R 1 L1 L2 2 3 R Y T G GROUND NEUTRAL NEUTRAL HOT HOT R7195 SUPPLY M944 G S LINE VOLTAGE MOTOR TERMINALS TO 4 20 mA INPUT B W R CW 135 OHM POTENTIOMETER INPUT M20791 ...

Page 6: ...the error signal voltage The balancing bridge circuit will amplify the error signal causing a Triac switch to fire This will energize a motor winding and will re position the feedback potentiometer until the error signal is reduced to zero Fig 8 Block diagram R7195A B MOTOR POSITIONER 5 4 6 G L2 L1 2 3 1 B W R 1 2 3 L1 L2 24 VAC 120 VAC Y T G GROUND NEUTRAL HOT R7195 SUPPLY M944B E MODUTROL MOTORS...

Page 7: ...tween the input signal and the slidewire signal is zero SERVICE AND TROUBLESHOOTING Calibration Procedure NOTE The R7195 Motor Positioner is calibrated at the factory for a 4 20 mA input signal for the R7195A and a 135 ohm potentiometer input for the R7195B Therefore do not calibrate the motor positioner unless the input signal desired is something other than 4 20 mA R7195A or 135 ohms R7195B To c...

Page 8: ...omponent failures are listed below a Shorted triac switches Q3 and Q4 b Q3 and Q4 break over at less than rated voltage c Q3 and Q4 do not fire d MOV CR12 shorts 5 If the logic diagram does not identify your system related problem the failure is not in the output circuit and the controller should be replaced or you may use the schematic to troubleshoot the board NOTE If your motor motor controller...

Page 9: ...O 1 REPLACE Q4 REPLACE Q4 DID MOTOR DRIVE AT NORMAL SPEED YES NO IS VOLTAGE LESS THAN 10V YES NO REPLACE Q3 A4 R28 R29 YES YES NO NO YES DID MOTOR DRIVE OPEN REPLACE Q4 REPLACE Q4 A5 R31 R32 REPLACE CR12 REPLACE Q3 M20795 NO YES SHORT TERMINALS B TO W CONNECT OPERATING VOLTAGE OPEN INPUT FROM CONTROLLER MEASURE AC VOLTAGE AT TERMINALS 1 AND L2 IS VOLTAGE LESS THAN 10V REPLACE Q3 YES NO YES NO YES ...

Page 10: ...AGE AT TERMINALS L2 TO 1 REPLACE Q4 REPLACE Q4 DID MOTOR DRIVE AT NORMAL SPEED YES NO IS VOLTAGE LESS THAN 10V YES NO REPLACE Q3 A4 R28 R29 YES YES NO NO YES DID MOTOR DRIVE OPEN REPLACE Q4 REPLACE Q4 A5 R31 R32 REPLACE CR12 REPLACE Q3 M20796 NO YES OPEN INPUT W CONNECT OPERATING VOLTAGE SHORT R W MEASURE AC VOLTAGE AT TERMINALS 1 AND L2 IS VOLTAGE LESS THAN 10V REPLACE Q3 YES NO YES NO YES DID MO...

Page 11: ...11 63 2582 ...

Page 12: ...ario M1V 4Z9 R7195A B MOTOR POSITIONER By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the lit...