background image

INSTALLATION INSTRUCTIONS

95-6046EF

® U.S. Registered Trademark
Copyright © 2002 Honeywell •  All Rights Reserved 

RP418A, B, C and RP818A, B

Electric/Pneumatic Relays

BEFORE INSTALLATION

The RP418 and RP818 Electric/Pneumatic Relays are 

electrically operated pneumatic switches used for interlock 
between an electrical system and a pneumatic control system. 

These devices can also be used as stop and bleed valves or 

as diverting or selector relays.

These relays are designed for wall mounting or panel 

mounting, depending upon the application. They can be 
mounted in any position without affecting the operation of the 

device. 

An optional 14003638-001 mounting kit is available for direct 

mounting to the MP516A operators, VP519C valves or 

PP901B and PP902B pressure regulators. See the Device 
Mounting section.

No special tools are needed to install the RP418 and RP818 
relays. Refer to job drawings for specific mounting locations.

INSTALLATION

Duct or Wall Mounting

1.

Position the relay on the duct or wall and mark the 

knockout mounting holes or mark the first hole and 
measure 1 in. (25mm) to the second hole. See Fig. 1.

2.

Drill holes for no. 8 mounting screws obtained locally.

NOTE: When wall mounting, use the mounting holes on the 

sides of the relay valve body or the knockout mount-

ing holes on the inside of the splice box. See Fig. 2.

3.

Attach the relay to the panel using mounting screws 

obtain locally.

Panel Mounting

1.

Line up the no. 8 mounting holes on the sides of the 

valve body with existing holes in the panel or drill new 

holes 1 in. (25 mm) apart. 

2.

Attach the relay to the panel using mounting screws 

obtained locally.

NOTE: The RP418 and RP818 are functional replacements 

for the RP417 and RP817. Note the difference in 

location of ports 1 and 2.

Fig. 1. RP418 and RP818 dimensions in in. (mm).

Device Mounting

The RP418 and RP818 Relays can be mounted directly to 

MP516 operators, VP519C valves, or PP901B and PP902B 
pressure regulators. A mounting bracket is available in 

adaptor kit 14003638-001. This bracket must be used when 

mounting the relay in this manner. 

1.

Use the mounting holes beneath the cover of the splice 

box and attach the relay using mounting screws 
obtained locally. See Fig. 2 through 5.

2-3/4

(71)

3-3/4 (96)

RP418A,C AND RP818A

1-5/8 (42)

RP418B; RP818B

1-1/4

(32)

1 (25)

5/8 (16)

7/8 DIAMETER 
KNOCKOUTS (2)
FOR 1/2 INCH 
CONDUIT

GROUNDING 
SCREW

KNOCKOUTS FOR 
NO. 8 SCREWS

1-3/8

(35)

1 (25)

7/16
(15)

1-1/4

(32)

1

1

1

MOUNTING CENTERS FOR NO. 8 SCREWS. MOUNTING CENTERS
MAY BE UP TO 1-5/16 (35) APART TO EASE INSTALLATION.

M18376

Summary of Contents for RP418B

Page 1: ...ned locally NOTE When wall mounting use the mounting holes on the sides of the relay valve body or the knockout mount ing holes on the inside of the splice box See Fig 2 3 Attach the relay to the panel using mounting screws obtain locally Panel Mounting 1 Line up the no 8 mounting holes on the sides of the valve body with existing holes in the panel or drill new holes 1 in 25 mm apart 2 Attach the...

Page 2: ...o 49 C either use 75 C rated wire or attach a close coupled 4 x 4 electrical box to the RP418A or RP818A splice box Make the wire splices within the electrical box Wire leads provide a means of connection on the RP418B and RP818B Use standard wire nut connectors obtained locally when making these connections NOTE A cord and plug are provided for wiring connections on the RP418C The RP418 and RP818...

Page 3: ...ARQUE Dans le cas d un montage mural utiliser les trous de montage situés sur les côtés du corps de la vanne du relais ou les ouvertures défonçables à l intérieur de la boîte de jonction Voir la Fig 2 3 Fixer le relais sur le panneau au moyen de vis de mon tage non fournies Montage sur panneau 1 Aligner les trous pour des vis de montage no 8 de chaque côté du corps de la vanne sur les trous déjà p...

Page 4: ...fil conçu pour une température de 75 C ou fixer une boîte électrique à couplage direct de 4 x 4 sur la boîte de jonction du RP418A ou RP818A Des fils conducteurs permettent de raccorder le RP418AB ou le RP818B Utiliser des raccords de fils à écrou non fournis avec ces conducteurs REMARQUE Un cordon avec fiche est fourni pour le raccor dement du RP418C Le RP418 et le RP818 ne nécessitent ni réglage...

Reviews: