EN0B-0356GE51 R1001

Copyright © 2001 Honeywell Inc. • All rights reserved

Excel IRC Excel 10

S7014A,B,C

SETPOINT ADJUSTMENT UNIT

Fig. 1. Setpoint adjustment unit S7014A

Fig. 2. Setpoint adjustment unit S7014B,C

GENERAL

The S7014A and B Setpoint Adjustment Units are designed
for unit mounting and are connected directly by a 2-meter-
long cable to the input of the Control Output Modules
R7452D,E,F.

The S7014A and B Setpoint Adjustment Units are used for
the manual adjustment of the room temperature setpoint. The
S7014B also allows the fan speed to be manually adjusted,
and is suitable for switching between automatic and manual
operation of a single-phase alternating current motors having
up to three speeds.

The S7014C has the same features as the S7014B, but the
resistance values are the same as those of the XL10/XL500
system.

MODELS

Function / Model no.

S7014A

1004

S7014B

1000

S7014C

1009

Remote setpoint adjustment

x

x

x

Fan speed control

x

x

Used in conjunction with

R7452D

R7452E,F

XL10,

XL500

SPECIFICATIONS

Remote setpoint
adjustment

-5...5 K

Fan speed control

Auto / OFF / ON1 /ON2 / ON3

Dimensions (H x W x D)

70 x 75 x 18 mm

Weight

80 g

Case

Plastic (ABS), flame-retardant as
per UL94-V0

Mounting

Wall, surface, or recess mounting

Ambient operating limits

0...+50 °C, 5...95% RH

Ambient storage limits

-25...+70 °C, 5...95% RH

Protection standards

IP30 as per DIN 40 050 or IEC 144

Connections

S7014A

unshielded cable, 2 m,
2 x 0.25 mm

2

S7014B

unshielded cable, 2 m,
3 x 0.25 mm

2

S7014C

unshielded cable, 2 m,
3 x 0.25 mm

2

PRODUCT DATA