background image

69-1174

2

S8701/S8702 DIRECT SPARK IGNITION CONTROLS

a

Valve used must be designed for DSI application.

b

Separate spark igniter and flame sensor mounted on a

common bracket.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on

the product to make sure it is suitable for your
application.

3. The installer must be a trained, experienced service

technician.

4. After installation is complete, check out system

operation.

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
If a new gas control is to be installed, turn off gas
supply before starting installation.
Be sure to conduct a gas leak test after the control
is installed.

CAUTION

Electric Shock Hazard.
Can cause personal injury or equipment
damage.
Disconnect power supply before wiring.

Model

No.

Spark

Igniter

Flame

Sensor

Valve Required

a

S8701/

Q347A

Q354A

Honeywell VR8205   

S8702

Q366

b

gas valves or
equivalent

Heat

Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control, see Table
2. If the appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should be
provided by the appliance manufacturer; verify proper air
circulation is maintained when the appliance is installed.

Table 2. S8701/S8702 Ambient Temperature Ratings.

IMPORTANT

If this is a replacement application, follow the
appliance manufacturer’s instructions, if avail-
able. The manufacturer usually provides wiring
diagrams, start-up and checkout instructions and
the service procedures for their system. If the
manufacturer’s instructions are not available, this
information may be used as a general guide.

Mounting The S8701/S8702 Control

Select a location within 6 ft (1.8m) of the burner that will
permit a direct cable route to the spark igniter terminal.
Ready access to the terminals is necessary for wiring and
servicing. The S8701/S8702 control may be mounted in
any position. Use No. 6-32 machine screws or No. 8
sheetmetal screws 1 inch long for fastening. Fasten
securely. Do not exceed the ambient temperature rating
given in Table 2.

M16233

13/16 (21)

1-1/8
(29)

2
(50)

2-13/16 (72)

3-15/16 (100)

3-3/8 (86)

3-3/8 
(86)

5/17 (7)

7/8 (23)

5-3/16
(130)

3/16 (4)

Operation

Ambient Temperature

50 Hz

-40

°

F to 160

°

F

60 Hz

-40

°

F to 175

°

F

Table 3. System Requirements.

Fig. 1. S8701/S8702 Dimensions.

Mounting Auxiliary Controls

Mount the spark igniter, flame sensor, temperature control,
transformer, gas control and any other auxiliary controls
according to the manufacturer’s instructions.

NOTE:

The S8701 and S8702 installations require a 24V
transformer rated to handle both the S8701/
S8702 current and the gas valve current. Table 4
shows the transformer rating necessary for
various loads.

Summary of Contents for S8701

Page 1: ...intenance section Review the following conditions that can apply to your specific installation and take the precautionary steps suggested Frequent Cycling This control is designed for use on commercial cooking appliances that typically cycle 400 times a day year round Perform a monthly checkout Water or Steam Cleaning If a control gets wet replace it If the appliance is likely to be cleaned with w...

Page 2: ...shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed Table 2 S8701 S8702 Ambient Temperature Ratings IMPORTANT If this is a replacement application follow the appliance manufacturer s instructions if avail able The manufacturer usually provides wiring diagrams start up and checkout instructions and the service proced...

Page 3: ...COMBINATION GAS CONTROL 2 0A MAX TEMPERATURE CONTOLLER LIMIT CONTROLLER TRANSFORMER M16232A FLAME SENSE ALARM VALVE GND VALVE GND 24 Vac GND 24 Vac BURNER GND SPARK ALARM IF USED Fig 2 S8701 Wiring Diagram Minimum VA Rating 24V transformer Total Valve Current in amperes S8701 S8702 in amperes 20 up to 0 6 0 15 30 0 6 to 1 0 0 15 40 1 0 to 1 4 0 15 55 1 4 to 2 0 0 15 Wiring General Precautions 1 Ch...

Page 4: ...d checkout procedures for other system components NOTE If one of the system components fail the S8701 S8702 will either not operate or it will go into safety lockout depending on the type of failure If the system does not perform as outlined in Start System and Check Trial for Ignition steps below refer to the SERVICE section to deter mine the cause Gas Leak Test If the gas control has been replac...

Page 5: ...rners for S8702 Shuts off spark after burner is lit The S8701 and S8702 are powered by a 24 Vac trans former and activated when the temperature control requests heat Operation is as follows When the S8701 S8702 control is activated by the temperature control s request for heat S8701 S8702 controls perform a safe start check that determines proper operation of the control before beginning the norma...

Page 6: ...BE SENSED AT BOTH BURNERS ON S8702 SPARK GENERATOR IS SHUT OFF LOCKOUT TIMER IS RESET IF FLAME CURRENT IS NOT SENSED B D J AND K MODELS GO INTO LOCKOUT AFTER ONE 1 TRIAL FOR IGNITION PERIOD LED IN ON SYSTEM MUST BE RESET MAIN BURNER OPERATION UNIT MONITORS BURNER FLAME CURRENT LOSS OF FLAME SPARK GENERATOR IS POWERED B D J AND K MODELS GO INTO LOCKOUT AFTER ONE 1 TRIAL FOR IGNITION PERIOD LED IS O...

Page 7: ...rol setpoint 5 F 3 C above room temperature Return setpoint to normal temperature setting or by re applying 24 Vac power to the S8701 S8702 control 5 Check ceramic insulator on flame sensor spark igniter or igniter sensor A cracked insulator will allow current to leak to ground Replace device if insulator is cracked START PREPURGE L AND M MODELS ONLY SAFE START CHECK TRIAL FOR IGNITION MAIN BURNER...

Page 8: ... they are clean and tight Grounding Connections A common ground is required for the burner spark igniter or igniter sensor mounting bracket the 24 Vac GND terminal and the GND burner terminal of the S8701 S8702 If ground is poor or erratic safety shutdown may occur occasionally even though operation is normal at time of checkout Therefore if nuisance shutdowns have been reported be sure to check g...

Page 9: ...e rod is immersed in the burner flame A bent flame rod bent mounting bracket or cracked ceramic insulator can affect flame signal Replace flame sensor if necessary Electrical Connections and Shorts Connections at the flame sensor must be clean and tight If wiring needs replacement use moisture resistant no 18 AWG wire rated for continuous duty up to 105 C 221 F Fig 8 Check Burner Flame Conditions ...

Page 10: ...CONTROL IF OKAY REPLACE GAS CONTROL NOTE IF UNIT GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF SENSOR CABLE S AND GROUND WIRES NOTE IF GROUND IS POOR OR ERRATIC SHUTDOWNS MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL AT TIME OF CHECKOUT CHECK FOR EXCESSIVE HEAT AT SENSOR INSULATOR S TEMPERATURE ABOVE 1000 F 538 C CAUSES SHORT TO GROUND IF CHECKS ARE OKAY REPLACE UNIT NOTE IF UNIT GOE...

Page 11: ...69 1174 11 S8701 S8702 DIRECT SPARK IGNITION CONTROLS ...

Page 12: ...neywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 69 1174 L C 4 99 Printed in Mexico Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com ...

Reviews: