S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
5
69-2075EF—01
1
Wiring harness G should be used if the control being
replaced has a 2-pin inducer/igniter connector instead of
a 4-pin inducer/igniter connector.
NOTE: To replace controls in Table 2, a jumper
(included with harness kit) may be required
to short out the rollout switch on the main 12-
pin connector plug from the furnace. The roll-
out switch is located between pins 5 and 11
on the 12-pin connector. Refer to Table 3 and
Fig. 2 on page 7.
INSTALLATION
When Installing This Product…
1.
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2.
Check the ratings given in these instructions to
make sure the integrated furnace control is suitable
for your application.
3.
Installer must be a trained, experienced service
technician.
4.
After installation is complete, check out operation
as provided in these instructions.
50A50-113
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
SW1: OFF
SW2: ON
50A50-295
SW1: ON
SW2: OFF
SW3: ON
SW4: OFF
50A50-296
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
50A50-408
SW1: OFF
SW2: OFF
SW3 & SW4: 60/90/
120/180
50A50-241
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
SW1: OFF
SW2: ON
50A55-143
G
SW1: ON
SW2: 30/60
SW3 & SW4: 60/90/
120/180
SW1: OFF
SW2: OFF
50A55-288
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
50A50-285
SW1: OFF
SW2: OFF
SW3: ON
SW4: OFF
50A55-285
G
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
Amana
1
10207701
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3: ON
SW4: OFF
SW1: OFF
SW2: ON
10207702
10207703
10207710
ICP
1010806
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3 & SW4: 60/90/
120/180
SW1: OFF
SW2: OFF
1380-686
SW1: OFF
SW2: ON
1380-699
SW1: OFF
SW2: ON
Lennox
1214201
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3: ON
SW4: OFF
SW1: OFF
SW2: OFF
Table 1. S9200U1000 Replaces These Integrated
Furnace Controls.
[Only use the S9200U1000 on 120 Vac applications.]
SKU
Harness
Field Settings
Recommendation -
DIP Switch S1
Safety
Timing
Settings -
DIP Switch
S2
Table 2. Replacing Additional Controls.
[Only use the S9200U1000 on 120 Vac applications.]
SKU
Harness
Field Settings
Recommendatio
n - DIP Switch
S1
Safety
Timing
Settings -
DIP Switch
S2
D330927P01
Jumper
(Roll-out
Switch)
A
Inducer & HSI
Connector
SW1: ON
SW2: OFF
SW3 & SW4: 60/
90/120/180
SW1: OFF
SW2: OFF
D330930P01
SW1: OFF
SW2: OFF
SW3 & SW4: 60/
90/120/180
SW1: OFF
SW2: ON
D330934P01
D340035P01
D340354P01
D340774P01
D341235P01
SW1: ON
SW2: OFF
SW3: ON
SW4: OFF
SW1: OFF
SW2: OFF
50A50-571
SW1: ON
SW2: OFF
SW3 & SW4: 60/
90/120/180
50A55-571
SW1: OFF
SW2: OFF
SW3: ON
SW4: OFF
50A50-473
SW1: OFF
SW2: OFF
SW3 & SW4: 60/
90/120/180
SW1: OFF
SW2: ON
50A50-474
50A50-405
50A50-406
50A50-471
50A55-474
SW1: OFF
SW2: OFF
SW3: ON
SW4: OFF
SW1: OFF
SW2: OFF
50A55-438
SW1: Check
Settings
SW2: OFF
SW3 & SW4: 60/
90/120/180
SW1: OFF
SW2: OFF