background image

S9361A207X INTEGRATED BOILER CONTROLLERS

69-2751—05

4

INSTALLATION AND 
CHECKOUT

When Installing This Product…

1.

Read these instructions carefully. Failure to 
follow them could damage the product or cause 
a hazardous condition.

2.

Check the ratings given in the instructions and 
on the product to make sure they are suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

1. The module can malfunction if it gets wet, 

leading to accumulation of explosive gas.
• Never install where water can flood, drip or 

condense on module.

• Never try to use a module that has been 

wet—replace it.

2. Liquefied petroleum (LP) gas is heavier than 

air and will not vent upward naturally.
• Do not light pilot or operate electric 

switches, lights, or appliances until you are 
sure the appliance area is free of gas.

3. If a new gas control is to be installed, turn off 

gas supply before starting installation. 
Conduct Gas Leak Test according to gas 
control manufacturer instructions after the 
gas control is installed.

4. If module must be mounted near moisture or 

water, provide suitable waterproof enclosure.

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.

Disconnect power supply before beginning 
wiring to prevent electrical shock or equipment 
damage.

Perform Preinstallation Safety 
Inspection

The preinstallation checks described in ANSI Standard 
Z21.71 

must

 be done before a replacement module is 

installed. If a condition which could result in unsafe 
operation is detected, the appliance should be shut off 
and the owner advised of the unsafe condition. Any 
potentially unsafe condition must be corrected before 
proceeding with the installation.

Maintenance Requirements in Severe 
Environments

Regular preventive maintenance is important in any 
application, but especially so in commercial, 
agricultural, and industrial applications, because:

1.

In such applications, particularly commercial, 
the equipment can operate 100,000 to 200,000 
cycles per year. Such heavy cycling can wear out 
the gas control in one to two years. A normal 
boiler application, for which the controls were 
intended, typically operate fewer than 10,000 
cycles per year.

2.

Exposure to water, dirt, chemicals, and heat can 
damage the module or the gas control and shut 
down the control system. A NEMA 4 enclosure 
can reduce exposure to environmental contami-
nants.

The maintenance program should include regular 
checkout of the system as outlined under Checkout. 

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

Do not attempt to take the module apart or to 
clean it. Improper reassembly and cleaning 
may cause unreliable operation, leading to an 
accumulation of explosive gas.

Maintenance frequency must be determined 
individually for each application. Some considerations 
are:

Cycling frequency.

 Appliances that may cycle more 

than 10,000 times annually should be checked 
monthly.

Intermittent use.

 Appliances that are used seasonally 

should be checked before shutdown and again before 
the next use.

Consequence of unexpected shutdown.

 Where the cost 

of an unexpected shutdown would be high, the system 
should be checked more often.

Dusty, wet, or corrosive environment. 

Since these 

environments can cause the controls to deteriorate 
more rapidly, the system should be checked more 
often.

Any control should be replaced if it does not perform 
properly on checkout or troubleshooting. In addition, 
replace any module if it is wet or looks like it ever has 
been wet. Protective enclosures as outlined under 
Planning the Installation are recommended 
regardless of checkout frequency.

Mount Module

Select a location close enough to the burner to allow a 
short (3 ft. [0.9 m] maximum), direct cable route to the 
igniter. Ambient temperature at the module must be 
within the range listed under Specifications. The 
module must be protected from water, moisture, 
corrosive chemicals and excessive dust and grease. 
Refer to Fig. 2 and 3 for recommended slot/hole 
pattern in appliance.

Summary of Contents for S9361A207 Series

Page 1: ...culator and Domestic Hot Water Circulator output Enabled with EnviraCOM communication capability to support remote monitoring and diagnostics Limit rated Temperature Sensing Probe One Sensor Model SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this...

Page 2: ...c 0 5 to 0 6 PF Ambient Ratings Humidity 0 to 95 percent relative humidity noncondensing Operating Ambient Temperature 4 F to 150 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 sec onds Flame Failure Response Time FFRT Maximum 2 5 seconds 1 µA Flame Lost Threshold 0 23 µA Accessories Ordered Separately W8735Y1000 Wireless Out...

Page 3: ...sary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity can cause the control to corrode...

Page 4: ...ecially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler application for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dirt chemical...

Page 5: ...EGRATED BOILER CONTROLLERS 5 69 2751 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Page 6: ...ic standoff insulators as required 1 Connect one end of the cable to the male quick connect SPARK terminal on the module 2 Connect the other end of the cable to the igniter or igniter sensor stud on the pilot burner igniter sensor Connect Vent Damper Vent Damper Models A vent damper can be used with modules provided with a vent damper plug connector The Molex plug provided simplifies wiring connec...

Page 7: ...etail Fig 4 Spark to Pilot Ignition Wiring S936X M533506 C R D DHW CIRCULATOR ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER OPTIONAL INDUCER OPTIONAL 24VAC TRANSFORMER SENSOR DHW T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL SPARK IGNITER FLAME SENSE MV ...

Page 8: ...n running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2secs part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is still off and the p...

Page 9: ...a three digit number and the corresponding degree designator See Display Readout Integrated Boiler Control One Rod Combined Ignitor and Sensor Model Displays See Table 6 8 for the IBC display screens Wait for vent damper to open 18 Damper actuator is energized and the system waits for damper to close Wait for vent damper to close 19 Damper actuator is de energize and the system waits for damper to...

Page 10: ...reen 3rd Screen StA State number Status bt Sensed temperature F or C Boiler Temperature SP Operating Setpoint F or C Operating Setpoint the lowest of the IQ Outdoor air reset EnviraCOM message Desired Boiler Setpoint high limit setpoint and setpoint from the remote user interface device HL_ High Limit F or C Adjust High Limit Setting HdF High Limit Differential F or C Adjust High Limit Differentia...

Page 11: ...mpound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other current carrying wires All wiring must comply with local codes and ordinances Disconnect power supply before beginning ...

Page 12: ...e heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 7 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sensor interface Boiler temperature which is utilized for High Limit funct...

Page 13: ...H OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED FLAME PROVED TIME OUT WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST RETRY DELAY TIME OUT A TIME OUT RECYCLE DELAY DAMPER PRESSURE SWITCH OPEN CHECK FLAME POST TRIAL FLAME DEB ON FLAME DEB OFF FLAME LOST A TIME OUT A TIME OUT TIM...

Page 14: ...out of posi tion restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for a d...

Page 15: ...s duringA D conversion Err 35 Duplicate Zone alarm was received from zone panel Err 55 Atmospheric Damper End Switch failed to close end switch contacts stuck open Err 56 Atmospheric Damper End Switch failed to open end switch contacts stuck closed Err 57 Flame Rod shorted to burner ground Err 58 AC line frequency error signal is too noisy or frequency is incorrect Err 59 Line voltage error voltag...

Page 16: ...risk Tamper evident tape has been placed on the bulk pack box to indicate if the package was opened Do not accept or use product received with damaged or missing tape Reverse engineering or modification of device is not permitted and may pose a safety risk LAZY YELLOW FLAME WAVING BLUE FLAME NOISY LIFTING BLOWING FLAME HARD SHARP FLAME SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM CLOGGED ORIFICE FI...

Reviews: