background image

S9361A207X INTEGRATED BOILER CONTROLLERS

69-2751—05

6

WIRING

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.

Disconnect the power supply before making 
wiring connections to prevent electrical shock 
or equipment damage.

Check the wiring diagram furnished by the appliance 
manufacturer for circuits differing from the wiring 
hookup shown in Fig. 4. Carefully follow any special 
instructions affecting the general procedures outlined 
below.

IMPORTANT

1. All wiring must comply with applicable local 

electrical codes and ordinances.

2. A common ground is required for the S93XX 

and the main burner. The 24V “secondary” 
plug internally grounds one side of the trans-
former. Any auxiliary controls or limits must 
not be in the grounded leg. In addition, the 
appliance should be earth-grounded.

3. Make sure the transformer has adequate VA. 

The ignition module requires at least 0.2A at 
24 Vac. Add the current draws of all other 
devices in the control circuit, including the gas 
control, and multiply by 24 to determine the 
total VA requirements of these components. 
Add this total to 5.0 VA (for the module). The 
result is the minimum transformer VA rating. 
Use a Class II transformer if replacement is 
required.

4. Check that L1 (hot) and L2 (neutral) are wired 

to the proper terminals.

Connect Ignition Cable (S936XAXXXX)

Use Honeywell ignition cable or construct an ignition 
cable that conforms to suitable national standards, 
such as Underwriters Laboratories Inc. See 
Specifications section. To construct a cable, fit one 
end (the module end) with 1/4 in. connector 
receptacle and the other with a connector to match 
the pilot assembly. Protect both ends with insulated 
boots.

NOTE:

Cable length must be 36 in. (0.9 m) or less. 
The cable must not be in continuous contact 
with a metal surface or spark voltage will be 
greatly reduced. Use ceramic or plastic 
standoff insulators as required.

1.

Connect one end of the cable to the male 
quick-connect SPARK terminal on the module.

2.

Connect the other end of the cable to the igniter 
or igniter-sensor stud on the pilot 
burner/igniter-sensor.

Connect Vent Damper (Vent Damper 
Models)

A vent damper can be used with modules provided 
with a vent damper plug connector. The Molex

®

 plug 

provided simplifies wiring connections.

To connect the vent damper, follow the wiring 
diagrams supplied with the vent damper for typical 
connections.

Connect Remaining Module 
Connectors

Connect remaining system components to the 
ignition module terminals as shown in the appropriate 
wiring diagrams, Fig. 4.

Connect Gas Control

Use No. 18 AWG or larger, depending on estimated 
curret draw, solid or stranded wire. Connect to gas 
control terminals as shown in wiring diagrams, using 
terminals appropriate to the gas control.

Ground Control System

The igniter/flame sensor and module must share a 
common ground with the main burner. Use AWM 
insulated wire with a minimum rating of 105°C 
(221°F) for the ground wire; asbestos insulation is not 
acceptable. If necessary, use a shield to protect the 
wire from radiant heat generated by the burner.

The burner serves as the common grounding area. If 
there is not a good metal-to-metal contact between 
the burner and ground, run a lead from the burner to 
ground.

NOTE:

“Earth” ground is not required.

Transformer: Add current ratings of module, gas 
control, vent damper and any other components of the 
control system to determine transformer size 
requirements.

Table 4. Specific Ignition Timings.

a

 Ignition Activation Period is the time that the hot surface igniter remains powered after the gas valve opens.

Purge Timing specified in seconds.

Model

Ignition 

Type

Draft Type

No. of 

Ignition 

Trials

Igniter/S

ensor 

Type

Automati

c Restart 

Time

Ignition 

Activatio

n Period

a

Prepurg

Timing

b

Postpurg

e Timing

b

S9360A

Intermittent 
Pilot - Spark

Induced

Infinite

Combined 1 hour

N/A

30

0

S9360A

Intermittent 
Pilot - Spark

Atmospheri
c

Infinite

Combined 1 hour

N/A

2.75

0

Summary of Contents for S9361A207 Series

Page 1: ...culator and Domestic Hot Water Circulator output Enabled with EnviraCOM communication capability to support remote monitoring and diagnostics Limit rated Temperature Sensing Probe One Sensor Model SPECIFICATIONS IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore an individual unit may not match the listed specifications exactly Also this...

Page 2: ...c 0 5 to 0 6 PF Ambient Ratings Humidity 0 to 95 percent relative humidity noncondensing Operating Ambient Temperature 4 F to 150 F Shipping Ambient Temperature 40 F to 175 F Flame Monitoring May vary by model Flame Establishing Period FEP Maximum 2 sec onds Flame Failure Response Time FFRT Maximum 2 5 seconds 1 µA Flame Lost Threshold 0 23 µA Accessories Ordered Separately W8735Y1000 Wireless Out...

Page 3: ...sary shield the controls to protect them from splashing water A NEMA 4 enclosure is recommended High Humidity or Dripping Water Over time dripping water or high ambient humidity can create unwanted electrical paths on the module circuit board causing the module to fail Never install an appliance where water can drip on the controls In addition high ambient humidity can cause the control to corrode...

Page 4: ...ecially so in commercial agricultural and industrial applications because 1 In such applications particularly commercial the equipment can operate 100 000 to 200 000 cycles per year Such heavy cycling can wear out the gas control in one to two years A normal boiler application for which the controls were intended typically operate fewer than 10 000 cycles per year 2 Exposure to water dirt chemical...

Page 5: ...EGRATED BOILER CONTROLLERS 5 69 2751 05 Fig 2 Recommended slot hole pattern in appliance in mm Fig 3 Align module with slots in manufacturer s control box 100 M24198 16 16 55 4 99 5 4 WATER HEATER CONTROL BOX M24229 ...

Page 6: ...ic standoff insulators as required 1 Connect one end of the cable to the male quick connect SPARK terminal on the module 2 Connect the other end of the cable to the igniter or igniter sensor stud on the pilot burner igniter sensor Connect Vent Damper Vent Damper Models A vent damper can be used with modules provided with a vent damper plug connector The Molex plug provided simplifies wiring connec...

Page 7: ...etail Fig 4 Spark to Pilot Ignition Wiring S936X M533506 C R D DHW CIRCULATOR ENVIRACOM SYSTEM CIRCULATOR L1 GND L2 DAMPER OPTIONAL INDUCER OPTIONAL 24VAC TRANSFORMER SENSOR DHW T STAT LIMIT SWITCH PRESSURE SWITCH PV PV MV GAS CONTROL SPARK IGNITER FLAME SENSE MV ...

Page 8: ...n running mode flame signal must be present Postpurge 9 System is purging at the end of a call for heat Inter purge Retry Recycle Delay 10 If the control loses flame signal during state 7 or 8 it will recycle through the 30 seconds purge time and last 2secs part of prepurge time Re Start delay due to flame failure Wait for pressure switch to open failed closed 11 The inducer is still off and the p...

Page 9: ...a three digit number and the corresponding degree designator See Display Readout Integrated Boiler Control One Rod Combined Ignitor and Sensor Model Displays See Table 6 8 for the IBC display screens Wait for vent damper to open 18 Damper actuator is energized and the system waits for damper to close Wait for vent damper to close 19 Damper actuator is de energize and the system waits for damper to...

Page 10: ...reen 3rd Screen StA State number Status bt Sensed temperature F or C Boiler Temperature SP Operating Setpoint F or C Operating Setpoint the lowest of the IQ Outdoor air reset EnviraCOM message Desired Boiler Setpoint high limit setpoint and setpoint from the remote user interface device HL_ High Limit F or C Adjust High Limit Setting HdF High Limit Differential F or C Adjust High Limit Differentia...

Page 11: ...mpound Honeywell part no 107408 to fill the space between the bulb and the well to improve heat transfer characteristics optional Make sure the sensor is held firmly in the well WIRING IMPORTANT For maximum trouble free operation run the sensor leadwires separately from any other current carrying wires All wiring must comply with local codes and ordinances Disconnect power supply before beginning ...

Page 12: ...e heating cycle returns to idle and waits for the temperature to drop again The circulator is turned on throughout the Call for Heat See Fig 7 for a graphical representation of a simple control cycle Note that the setpoint differential may vary based on OS number High Limit Controller All models include a 3 wire temperature sensor interface Boiler temperature which is utilized for High Limit funct...

Page 13: ...H OR CALL FOR HEAT LOST SWITCH OPEN SWITCH CLOSE SWITCH OPEN FLAME DEB ON FLAME DEB OFF TIME OUT TIME OUT OR MANUAL RESET LIMIT SWITCH OPEN TIME OUT FLAME SENSED FLAME PROVED TIME OUT WATER TEMPERATURE HIGH OR THERMOSTAT CALL FOR HEAT LOST RETRY DELAY TIME OUT A TIME OUT RECYCLE DELAY DAMPER PRESSURE SWITCH OPEN CHECK FLAME POST TRIAL FLAME DEB ON FLAME DEB OFF FLAME LOST A TIME OUT A TIME OUT TIM...

Page 14: ...out of posi tion restore to correct position STEP 3 Check spark ignition circuit Disconnect the ignition cable at the SPARK terminal on the module WARNING The ignition circuit generates over 10 000 volts and electrical shock can result Energize the module and listen for the audible sparking noise When operating normally there should be a buzzing noise that turns on and off twice per second for a d...

Page 15: ...s duringA D conversion Err 35 Duplicate Zone alarm was received from zone panel Err 55 Atmospheric Damper End Switch failed to close end switch contacts stuck open Err 56 Atmospheric Damper End Switch failed to open end switch contacts stuck closed Err 57 Flame Rod shorted to burner ground Err 58 AC line frequency error signal is too noisy or frequency is incorrect Err 59 Line voltage error voltag...

Page 16: ...risk Tamper evident tape has been placed on the bulk pack box to indicate if the package was opened Do not accept or use product received with damaged or missing tape Reverse engineering or modification of device is not permitted and may pose a safety risk LAZY YELLOW FLAME WAVING BLUE FLAME NOISY LIFTING BLOWING FLAME HARD SHARP FLAME SMALL BLUE FLAME CHECK FOR LACK OF GAS FROM CLOGGED ORIFICE FI...

Reviews: