SD500-PS and SD500-PSDA
Addressable Fire Pull Station 
Installation Instructions

The SD500-PS is an single action addressable 
fire pull station and the SD500-PSDA is a dual 
action addressable fire pull station. The SD500-
PS and SD500-PSDA are a normally open 
initiating point that is compatible with 
Honeywell Silent Knight and Farenhyt Series 
addressable fire alarm control panels (FACP). 

The SD500-PS/PSDA are designed for indoor 
use in non-explosive environments. Used to 
activate a non-coded alarm instantly.

An on-board status LED is visible from the front 
of the pull station. The LED flashes to indicate 
proper communication with the FACP 
(approximately every 30 seconds).

Specifications

Operation

To activate the fire pull station:

1. Grab the top of the pull station where it is 

labeled “PULL”.

2. Pull the cover plate out and down.

To reset the pull station:

1. Insert key into the lock.

2. Turn the key clockwise.

3. Close the cover plate.

4. Turn the key counter clockwise.

Wiring to the SD500-PS/PSDA

Wire the SD500-PS as shown in Figure 1.

Figure 1: Fire Pull Station Wiring

Mounting the SD500-PS/PSDA

The pull station mounts to a standard single gang 
electrical switch box or a surface mount back 
box P/N PS-SMBB (sold separately). See Figure 
2.

Parameter

Rating

Max. Line resistance

50

Max. Alarm 
Current

One device in 
alarm 23mA. 46 
mA for two 
devices in alarm.

.5 mA for each 
additional device in 
alarm.

Max. Voltage

33 V

Operating Temperature

0° to 49° C
(32° to 120° F)

Dimensions

5-1/8” H x 3-1/16” W x 1.5” D

Parameter

Rating

Supervised
Power Limited