Operation
SDC / DHC
100 EN2H-0221GE51
R0808
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
1
Minimum limit based on
request
1
2
Limited minimum limit
05 Limit
mode
minimum limit (not
if parameter 01 =
OFF)
3
Unlimited minimum limit
1
Burner switch-off in case
of defect
1
2
External burner switch-
off
06 Sensor
operating
mode
3
Burner enable in case of
defect
07 Minimum
burner
runtime
0 ... 20 min
2
One stage: 2 ... 30 K
6
08 Burner
switching
differential I
Two stages: 2 ... (setting value of
parameter 09 – 0.5 K)
09 Burner
switching
differential II (not if
parameter
01 = 2)
(setting value of parameter 08 +
0.5) to 30 K
8
10 Connection
delay
stage II
0 ... 60 min (0 = 10 s)
0
1
Unlimited enable during
start-up relief
2
11 Boiler
start-up
relief stage II
2
Time-out during start-up
relief
1 Two-stage
hot-water
circuit charge (with delay
of full-load stage)
1
2
Two-stage hot-water cir-
cuit charge (unlimited)
12
Storage charge
1–2 stages
3 One-stage
hot-water
circuit charge (partial
stage only)