Technical data
SDC / DHC
252 EN2H-0221GE51
R0808
8.2.2 PT
1000
For variable input 1 (VI-1) (setting of exhaust gas sensor),
collector flow sensor (SPFS)
°C
Ω
°C
Ω
°C
Ω
°C
Ω
0
1000.00 80
1308.93 140
1535.75 280
2048.76
10
1039.02 85
1327.99 150
1573.15 300
2120.19
20
1077.93 90
1347.02 160
1610.43 320
2191.15
25
1093.46 95
1366.03 170
1647.60 340
2261.66
30 1116.72
100 1385.00
180 1684.65
360 2331.69
40 1155.39
105 1403.95
190 1721.58
380 2401.27
50 1193.95
110 1422.86
200 1758.40
400 2470.38
60 1232.39
115 1441.75
220 1831.68
450 2641.12
70 1270.72
120 1460.61
240 1904.51
500 2811.00
75 1289.84
130 1498.24
260 1976.86
– –
8.3 Sensor measurement ranges
Designation
Brief description
Sensor type
Measurement
range
Outside sensor
AF
NTC 20
–50 °C to 90 °C
Heat generator sensor
KF
NTC 20
–50 °C to 120 °C
Flow sensor 1
VF1
NTC 20
–50 °C to 120 °C
Flow sensor 2
VF2
NTC 20
–50 °C to 120 °C
Tank sensor
SF
NTC 20
–50 °C to 120 °C
Collector flow sensor
KVLF
PT 1000
–50 °C to 210 °C
Collector tank/buffer
sensor
KSPF
NTC 20
–50 °C to 120 °C
Variable input VI-1*)
VE1
NTC 20
PT 1000
–50 °C to 120 °C
–50 °C to 500 °C
Variable input VI-2
VE2
NTC 20
–50 °C to 120 °C
Variable input VI-3
VE3
NTC 20
–50 °C to 120 °C
*) Depending on the selection of the assigned function.
PT 1000 e.g. for exhaust gas sensor connection.