SEC-H-600 SECURITY CONTROLLER
15
95-7759—07
SECURITY I/O WIRING
Security I/O wiring is covered in the following subsections:
• “Door Terminal Associations,” page 15
Door Terminal Associations
The SEC-H-600 controller provides access control for two doors. For each door, the controller
allocates
:
• One Reader Input (for a Wiegand-type, 12V reader)
• Two Supervised Inputs: one for door switch monitor, one for REX (request-to-exit)
• One Relay Output: for door strike control.
A default convention is used for the logical association between reader inputs, supervised inputs, and relay outputs for each door,
as shown in Table 4 below.
NOTE: Terminal associations shown in Table 4 also apply if wiring a SEC-H-R2R (2 reader) expansion module.
See the following sections below for more details:
• Example Door 1 Wiring
• Other Terminal Associations
Table 4. Door mapping to security I/O terminal points.
Door
Reader Input
Supervised Input Terminals
(with GND)
Relay Output Terminals
Door Lock
Door Switch
Monitor
Request to Exit
(REX)
Door 1
Card Reader 1
SI1
SI2
1 (C1 and NO1, or NC1)
Door 2
Card Reader 2
SI3
SI4
2 (C2 and NO2, or NC2)