SEC-H-600 SECURITY CONTROLLER
17
95-7759—07
Reader Input
The SEC-H-600 controller has two door reader inputs, each supporting a Wiegand-type 12Vdc reader. Each reader input has a 7-
position connector, on the circuit board labeled as Card Reader 2 and 1 (see Fig. 4 on page 12). Typical wiring is shown below in
Fig. 8. Pinouts for each card reader connector are shown in Table 5.
NOTE: A door wired to a reader input has other I/O points, see “Door Terminal Associations,” page 15.
Fig. 8. Reader wiring to Security Controller.
Reader Wiring Notes
• Mount the reader, referring to the specific manual for that reader for instructions.
• Use shielded, twisted-pair, cabling (Belden #8725 or #8723 or equivalent, as needed) to connect the reader to the Security
Controller. Maximum cable distance is 500 feet (152m).
• Run this cabling from the reader to the Security Controller, bringing it through an appropriate knockout in the enclosure used.
Allow sufficient slack cable for servicing.
• Tie all shield wires together, and connect to the designated grounding point at the enclosure. SeeFig. 5 on page 13.
• Place the appropriate wires in the appropriate screw terminals of the 7-position reader connector. Refer to the pinouts in
Table 5 above for reader input designations. Figure 8 above lists typical wiring colors.
Table 5. Pinouts for Card Reader Inputs
Terminal
Terminal Name
Terminal Notes
Typical cabling colors
DC+
+12Vdc to Reader
Always wire these four terminals to the
corresponding reader terminals.
Typically Red wire.
GND
Ground
Typically Black wire.
D0
Reader Data 0
Typically Green wire.
D1
Reader Data 1
Typically White wire.
AX1
Auxiliary 1
Optional, wire to reader’s
Green LED
control
At reader, typically Orange wire.
AX2
Auxiliary 2
Optional, wire to reader’s
Red LED control
At reader, typically Brown wire.
AX3
Auxiliary 3
Optional, wire to reader’s
Beeper control
At reader, typically Blue or Yellow
wire.
GN
D
DC+
AX3
AX1
D1
AX
2
D0
CARD
R
E
ADE
R
n
Red
(
+
12Vd
c)
Bl
ack
(G
round
)
Gr
een
(Dat
a 0)
Wh
ite
(
D
at
a
1)
op
tio
nal 1
op
tional 2
op
tional 3
Reader
Shields
NOTE:
Maximum current rating for
both reader inputs (combined) is:
• Peak current maximum:
0.40A
• Average current maximum:0.30A