background image

SEC-H-INT-KP SMARTKEY

62-0272—01

2

MOUNTING

Mount the SEC-H-INT-KP backplate onto a wall junction box, 

with wiring cable(s) passed through center opening. See 

Figure 2 for dimensions.

Fig. 2. SEC-H-INT-KP backplate dimensions.

Fasten with the appropriate screws into the mounting slots.

WIRING

Only two connectors on the back of the SEC-H-INT-KP 

(Figure 3) are used: J1 (Power) and J5 (RS-485 comm).

Fig. 3. Connector Detail, Rear View of SEC-H-INT-KP.

Connectors have pre-attached leads—make wiring 

terminations to leads using small wire nuts. Lead colors are 

shown (in parenthesis) in Figure 3.

CAUTION

Electrical Shock Hazard

Before making wiring terminations, remove power 

from the security controller or SEC-H-R2R module. 

Restore power only after making all wiring 

terminations and fastening the SEC-H-INT-KP 

SmartKey unit onto its mounted backplate.

Note that up to 10 SEC-H-INT-KP SmartKey units are 

supported, where RS-485 wiring from the security controller 

(NPB-2X-485 option card) is “daisy-chained” at the data J5 

connector on each SmartKey. For any SmartKey installed on 

either end of this RS-485 buss, set its EOL Resistor JUMPER 

1 to the ON position.

Wire 12VDC power to the unit from the reader input of the 

security controller, or if closer, the reader input of an SEC-H-

R2R module. Use shielded, twisted-pair cabling for all wiring, 

with the shield continuously connected and grounded to earth 

at one point only. See “Recommended Cable Types,” page 1.

M27320

31/64

(12)

3-5/32 (80)

Ø 1/64 (4)

1-3/16

(30)

2-23/64 (60)

31/64

(12)

5

(127)

2-23/64

(60)

31/64

(12)

31/64

(12)

1

2

3

1

2

3

1
2
3
4
5

1

2

3

1

2

3

1

2

3

4

5

1

2

3

4

1

2

3

5

6

1

2

3

J5

J6

J7

J1

J2

J3

J4

M27321

J5 DATA

(SHIELD) EARTH
(GREEN) DATA (–)
(YELLOW) DATA (+)

J1 POWER

(YEL/GRN) EARTH GND
(BLACK) GND
(RED) + 12V-15 VDC

Summary of Contents for SEC-H-INT-KP

Page 1: ... does NOT communicate on the same RS 485 bus as the SEC H R2R and SEC H RIO modules A maximum of 10 SmartKeys may be installed per security controller Not covered in this document is the setup and operation of installed SEC H INT KP SmartKeys Refer to the WEBs AX Security Controller User s Guide number 74 4062 for this information For all other related mounting and wiring details refer to the appr...

Page 2: ...and fastening the SEC H INT KP SmartKey unit onto its mounted backplate Note that up to 10 SEC H INT KP SmartKey units are supported where RS 485 wiring from the security controller NPB 2X 485 option card is daisy chained at the data J5 connector on each SmartKey For any SmartKey installed on either end of this RS 485 buss set its EOL Resistor JUMPER 1 to the ON position Wire 12VDC power to the un...

Page 3: ... for setup procedures RELATED DOCUMENTATION For more information on mounting and wiring a WEBs Security system refer to the following documents SEC H 201 Security Controller Installation Guide 95 7750 SEC H 600 Security Controller Installation Guide 95 7759 SEC H R2R Remote Reader Module Installation Guide 95 7749 SEC H RIO Remote I O Installation Guide 74 4060 SEC ENC H 1 and SEC ENC H 2 Medium a...

Page 4: ...red Trademark 2008 Honeywell International Inc 62 0272 01 M S 03 08 By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting fro...

Reviews: