Introduction
Outputs
Analog output
0 to 22 mA sink or source (configurable)
Digital output
Modbus RTU
Relay output
5 A, 250 V AC, 24 V DC
The two relays can be used for fault signalling (normally energized) or
for alarm signalling. The relay assignments and operations are
configurable using the mobile app.
Modbus RTU Default Communication Setting
Baud rate
9600
Parity
Even
Data bits
8
Stop bits
1
Flow control
none
Relay Default Setting
Relay 1
Any faults and initial state is energized.
Relay 2
Gas alarm 1 and initial state is de-energized.
Maximum Power Consumption
The power consumption varies, depending on output version and
sensor type. The additional maximum power consumption for the relay
output version is 0.6 W.
Analog Output Version
In normal state
During an alarm
Electrochemical-cell-type sensors
0.5 W
1.2 W
Catalytic-type sensors
1.0 W
1.7 W
Infrared-type sensors
1.0 W
1.7 W
Digital Output Version
In normal state
During an alarm
Electrochemical-cell-type sensors
0.3 W
0.7 W
Catalytic-type sensors
0.8 W
1.2 W
Infrared-type sensors
0.8 W
1.2 W