Detector Parameters
Sensepoint XRL’s UL 2075 approval
Sensepoint XRL was evaluated for UL 2075. The evaluation is valid only
with:
• CO
• CH
4
(Catalytic bead sensor)
• 4–20 mA output with 250
Ω
load resistor
To guarantee Sensepoint XRL’s long-term compliance for UL 2075, at
least twice a year (6 months interval) gas calibration is required. UL
2075 alarm setting of Sensepoint XRL is:
• CO alarms between:
–
60 to 240 min @ 70 ppm
–
10 to 50 min @ 150 ppm
–
4 to 15 min @ 400 ppm
• Methane alarms: Less than 25 %LEL
43