background image

User Manual

Carbon Monoxide Alarm

Model SF340 Series

CAREFULLY READ AND UNDERSTAND THE CONTENTS OF THIS 

INSTRUCTION MANUAL BEFORE USING THE ALARM.

RETAIN THE MANUAL IN A SAFER PLACE FOR FUTURE  

REFERENCE. PAY PARTICULAR ATTENTION TO THE SAFETY  

WARNINGS. BE SURE TO PASS THE MANUAL ONTO ANY  

SUBSEQUENT USERSOF THE ALARM.

WHEN INSTALLING THIS ALARM FOR USE BY OTHERS PLEASE 

LEAVE THIS MANUAL OR A COPY WITH THE END USER.

This manual covers the following models:

SF340E

  

230V, 50Hz Standard Model

SF340F

  

230V, 50Hz Output Model

 

(for relay and interconnect feature)

SF340J

  

12/24Vdc Output Model

 

(for relay and interconnect feature)

Each of the models above comes complete with:

SF340M

  

Carbon Monoxide Sensor Module including battery 

 

back-up and electrochemical gas sensing system.

WARNING

Actuation of your Carbon Monoxide (CO) alarm  

indicates the presence of Carbon Monoxide (CO)  

which can KILL YOU.

THIS Carbon Monoxide ALARM MAY NOT PROTECT PEOPLE WHO 

ARE AT SPECIAL RISK BY REASON OF AGE, PREGNANCY OR 

MEDICAL CONDITION. THESE INDIVIDUALS MAY CONSIDER US-

ING WARNING DEVICES WHICH PROVIDE AUDIBLE AND VISUAL 

SIGNALS FOR Carbon Monoxide CONCENTRATION UNDER 

30PPM. IF IN DOUBT PLEASE CONTACT YOUR  

MEDICAL PRACTITIONER. A Carbon Monoxide ALARM IS NOT A 

SUBSTITUTE FOR A SMOKE ALARM OR A COMBUSTIBLE  

GAS DETECTOR.

This Carbon Monoxide alarm is designed to detect Carbon  

Monoxide gas from any source of combustion including wood, 

coal, coke, oil, petrol and gas.

This Carbon Monoxide Detector is 

NOT

•   Designed to detect smoke fire or any other gas.

•   To be seen as a substitute for the proper servicing of fuel-burning

 

  appliances or the sweeping of chimneys.

•   To be used on an intermittent basis, or as a portable alarm for the  

  spillage of combustion products from fuel burning appliances or 

  chimneys.

CAUTION

This Carbon Monoxide alarm is designed for indoor use only. Do not 

expose to rain or moisture. Do not knock or drop the alarm. Do not 

tamper with the alarm as this could cause electric shock or alarm 

malfunction. The alarm will not protect against the risk of Carbon 

Monoxide poisoning when the battery back up is no longer  

functioning. This alarm will only indicate the presence of Carbon 

Monoxide gas at the sensor. Carbon Monoxide gas may be present 

in other areas. Do not paint.

TESTING YOUR ALARM

A green power light indicates power is supplied. The alarm should be 

tested weekly by pushing and holding the test button on the front of 

the unit. The alarm signal should sound. If relay models are in use or 

units are interconnected please be aware that the relay function will be 

activated upon test.

CARE AND MAINTENANCE OF ALARM

The outside casing of the alarm should be wiped occasionally with a 

cloth. Ensure that the holes on the front are not blocked with dirt and 

dust. DO NOT USE CLEANING AGENTS, BLEACH OR POLISH.

IMPORTANT

•   Ideally it is recommended that a Carbon Monoxide alarm should  

 

be installed in or near to every room which contains a fuel burning 

 

appliance such as gas fires, central heating boilers, room heaters,

 

 

water heaters, cookers, grills etc

•   Ensure that the alarm buzzer can be heard by all those who are

 

 

intended to hear it.

•   Seek medical help if it is suspected that a member of the 

 

 

household is suffering from Carbon Monoxide poisoning.

IF FURTHER DETAILS ARE REQUIRED THAT DO  

NOT APPEAR IN THIS MANUAL PLEASE CONTACT  

HONEYWELL ANALYTICS.

PACK CONTENTS

Models SF340E, SF340F, SF340J will contain:

One alarm

One Sensor Module (SF340M)

One instruction manual

One installation kit, consisting of:

 

Two wall plugs

 

Two wall fixing screws

 

Two electrical mounting screws

SPECIFICATION

Models:  

 

 

SF340E,F,J

Gas Detected:  

 

Carbon Monoxide

Detection Principle:  

 

Electro-chemical cell

Alarm Indication:  

 

Flashing red light and audible  

 

 

 

 

alarm

Alarm Levels:  

 

150ppm  

Between 10 and  

 

 

 

 

 

30 minutes

 

 

 

 

350ppm  

Within 6 minutes.  

 

 

 

 

 

(as required by  

 

 

 

 

 

BS7860: 1996)

Supply Voltage Range:  

 

SF340E,F 

220/240Vac,   

 

 

 

 

50Hz

 

 

 

 

SF340J  

12Vdc ±10% or  

 

 

 

 

 

24Vdc ±10%

Operating Temperature:   

-5ºC to 40ºC.

Humidity Range:  

 

30 to 90% RH.

Warm-up Time after Initial Switch On:  

Instantaneous.

Normal Module Operating Life:  

5 years.

Backup Battery Life when in Alarm:  

At least 5 days.

Dimensions:   

 

170mm x 110 mm x 65mm.

Weight:  

 

 

Approximately 575g.

DISPOSAL WARNING: Do not dispose of in fire

GUARANTEE

We guarantee your new gas alarm for five years, from the date 

of purchase and under normal use and service, to be free from 

defects in materials and workmanship. During this period we will, 

at our discretion, repair, replace of refund the price of any part of 

the gas alarm which is found to be defective in either materials or 

workmanship providing this occurs under normal use and service. 

We shall, however, be under noobligation to repair, replace or 

refund the price of units which are found to be defective in any way 

due to damage, neglect, unreasonable use or which have been 

tampered with or found to have been dismantled. Defective units 

should be returned, in suitable packaging, along with proof of  

purchase to Honeywell Analytics, 4 Stinsford Road, Nuffield 

 

Industrial Estate, Poole, BH17 0RZ. An accompanying letter should 

state clearly any problem with the gas alarm. This guarantee does 

not affect your statutory rights.

INTRODUCTION

Thank you for purchasing this alarm which is designed to detect 

the presence of Carbon Monoxide (CO) gas. This manual contains 

information on the installation and the operation of the SF340 

modular Carbon Monoxide alarm.

THIS ALARM SHOULD ONLY BE INSTALLED

BY A COMPETENT PERSON

ALL ELECTRICAL WIRING SHOULD BE INSTALLED

IN ACCORDANCE WITH THE CURRENT WIRING REGULATIONS OF 

THE INSTITUTE OF ELECTRICAL ENGINEERS

1. WHAT IS CARBON MONOXIDE?

Carbon Monoxide is a highly poisonous gas which is released 

when fuels are burnt. It is invisible, has no smell and no taste, 

therefore it is very difficult to detect with the human senses.

Potential danger areas in your home

Gas, coal  
or wood  
fire

Boiler or 
Heater

Water 
Heater

Portable gas 
or paraffin 
heater

Clogged 
chimney 
or flue

Car fumes 
from 
garage

Portable  

cooking  

equipment 

used in  

enclosed areas

Kitchen 
cooker

Under normal operating conditions, in a room where fuel  

burning appliances are well maintained and correctly ventilated, 

the amount of Carbon Monoxide released by the appliances is  

not dangerous.

A dangerous quantity of Carbon Monoxide can occur if one or 

more of the following conditions exists:

1. An appliance is faulty or badly maintained.

2. A flue is partially or totally blocked.

3. A room is not adequately ventilated.
The following conditions can result in transient Carbon Monoxide 

situations:
1.  Excessive spillage or reverse venting of fuel burning appliances  

    caused by outdoor ambient conditions such as:
    i. Wind direction and/or air velocity; including high gusts of    

      wind. Heavy air in the vent pipes(cold humid air with  

 

      extended periods between cycles)
  ii.   Negative pressure differential resulting from use of exhaust fans.
  iii.   Simultaneous operation of several fuel burning appliances   

      competing for limited internal air.
  iv.   Flue connections breaking loose from clothes dryers, water  

      heaters or boilers.

  v.   Obstructions in or unconventional flue designs which can    

      amplify the above situations.
2.  Extended use of unvented fuel burning devices.
3. Temperature inversions which can trap exhaust gases near the 

    ground.
4. A car running in an open or attached garage near a home.

2. WHAT ARE THE SYMPTOMS OF CARBON MONOXIDE POISONING?

The following symptoms are related to Carbon Monoxide  

poisoning and should be discussed with ALL members of the 

household:

Mild exposure:

  

Slight headache, nausea, vomiting, fatigue 

   

 

(often described as “flu-like” symptoms)

Medium exposure:

  

Severe throbbing headache, drowsiness,  

   

 

confusion, fast heart rate.

Extreme exposure:

   Unconsciousness, convulsions,  

   

 

cardiorespiratory failure, death.

Many reported cases of Carbon Monoxide poisoning indicate that 

while victims are aware they are not well, they become so  

disorientated that they are unable to save themselves by either 

exiting the building or calling for assistance. It is also important to 

note that young children and pets may be the first to be affected.

3. IN WHICH ROOM SHOULD I PUT THE ALARM?

Ideally you should have an alarm in or near every room which 

contains a fuel-burning appliance.
However, if you have more than one appliance but only one alarm, 

you should take the following into consideration when deciding 

where best to put the alarm:

•   If there is a fuel burning appliance in a room where people    

  sleep, you should put the alarm in that room.

•   If there is a fuel burning appliance in a room you use a lot

 

  such as a sitting room, you should put the alarm in that room.

•   If you live in a bed-sit put the alarm as far away from the

 

  cooking appliance as possible, but near to the room where 

  you sleep.

•   If the fuel burning appliance is in a room not normally used

 

  (e.g. a boiler room) put the alarm just outside the room so you  

  will be able to hear it.

4. WHERE SHOULD I PUT THE ALARM?

Carbon Monoxide has a similar density to warm air. To ensure the 

most effective use is made of the alarm it should be fitted at least 

1.5m (5’) above floor level and at least 1.85m (6’) from the fuel 

burning appliance. Warm air naturally rises; it is better to install the 

unit higher rather than lower. The SF340 Series can be fitted on the 

wall or on the ceiling.

ALARM

1.85m

(6’)

(min)

1.5m

(5’)

(min)

5. WHERE NOT TO PUT THE ALARM

Do not place the alarm in the following areas:

•   Outside the building.
•   In or below a cupboard.
•   In a damp or humid area.
•   Directly above a sink or cooker.
•   Next to a door or window or anywhere it could be affected    

  by drafts.

•   Where the airflow to the alarm could be obstructed by curtains  

  or furniture.

•   Where dust or dirt could collect and block the sensor.
•   Where the temperature could drop below -5ºC or rise above  40ºC.
•   Where it could be easily knocked or damaged.
•   Within 1.5m (5 feet) of any cooking appliance.

6. OPERATING OF THE ALARM

The detector is not fitted with an on/off switch, it is automatically 

switched on when the power source is activated. This is to ensure 

the detector can not be inadvertently switched off and therefore 

fail to detect a build up of Carbon Monoxide.

Normal operation

When the unit is powered from the primary power source (e.g. 

230Vac, 12/24Vdc), the green light will be illuminated. (The green 

light will not be illuminated when the battery backup is in use.)

When no Carbon Monoxide is present the red alarm light will flash 

approximately once every 60 seconds. This indicates the alarm is 

working correctly.

Alarm conditions

When the unit detects Carbon Monoxide, the alarm signal is given 

continuously. The red light will flash and the buzzer will sound.

When the unit has been in alarm for a period of 40 minutes, the 

alarm signal will be given once every 60 seconds.

Return to normal operation

When the Carbon Monoxide disperses, the alarm will automatically 

stop. The red light will flash approximately once every 60 seconds 

(normal operation.)

Battery replacement warning

When the backup battery in the SF340M module needs replacing the 

audible alarm will sound a single short beep once every 60 seconds. 

The battery must then be replaced. The red light will flash once every 

60 seconds as normal. See Section 10 on batteries.

Module replacement warning

When the module (SF340M) needs replacing, the audible alarm will 

sound two short beeps every 60 seconds. At this time the module 

must be replaced. The red light will flash once every 60 seconds as 

normal.

7. SF340 SERIES FEATURES

All units are powered by a primary power source (e.g. 230V or 

12/24Vdc) and contain a replaceable Module which houses the 

battery backup and gas sensing systems.

POWER LIGHT (all SF340 models)

The green power light will illuminate when the primary power 

source is connected and working (230V or 12/24Vdc according to 

model). This light will illuminate even when the Module is not fitted.

ALARM/CONFIDENCE LIGHT (all SF340 models)

In normal operation the red light will flash once per minute to 

indicate that the unit is operating correctly. This light will flash 

whether the Module is powered from the primary power source or 

the battery backup. In the alarm condition it will flash five times 

per second.

AUDIBLE ALARM (all SF340 models)

In the alarm condition the buzzer will sound. Models SF340E, 

SF340G and SF340H will sound the Morse Code signal for ‘CO’ 

(– • – • – – –). Models SF340F and SF340J will give a continu

-

ous buzzer sound and this will continue for 90 seconds after the 

alarm light has stopped. Where models SF340F and SF340J are 

interconnected, all units connected will sound the continuous 

alarm signal. Only units in alarm will have a continuously flashing 

alarm light.

BATTERY BACKUP (all SF340 models)

All models in the SF340 series have a battery backup feature. This 

powers the alarm in the event of a primary power failure (230V or 

12/24Vdc according to model).

TEST BUTTON (all SF340 models)

All models in the SF340 series have a test button. This is 

positioned on the front of the unit and when pushed will cause 

the audible and visual alarm signals to be given. If the relay and 

interconnect options are used, these will also operate when the 

test button is pressed. Note that for models SF340F and SF340J 

the buzzer will sound and the relay will operate for 90 seconds.

RELAY OUTPUT (Models SF340F & SF340J)

The relay provides a single pole changeover (SPCO) volt free 

contact which can be used to signal to a control panel or switch 

an external siren or gas valve. The relay contacts are rated at 3A 

/ 230Vac and will change state when the unit goes into the alarm 

condition or when the test button is pressed. When the unit comes 

out of the alarm condition the relay will automatically revert to its 

original state after a delay of 90 seconds.

INTERCONNECT (Models SF340F & SF340J)

The interconnect facility enables up to 20 SF340F or SF340J 

alarms to be connected together. If one unit goes into the alarm 

condition the audible alarm on all interconnected units will sound. 

This alarm signal is a continuous tone. The unit that caused the 

alarm can be identified as it will be the only one with a 

 

continuously flashing alarm light. When the unit comes out of the 

alarm condition the alarm light will stop giving the alarm signal. 

After a delay of 90 seconds the buzzers of all interconnected units 

will stop sounding and the relays will reset.

8. HOW SHOULD I INSTALL MY ALARM?

ELECTRICAL BOX MOUNTING HOLES

CABLE ENTRY POINTS

WALL FIXING HOLES

A. Mounting

Select a suitable location to install the alarm (see Section 4 

‘WHERE SHOULD I PUT THE ALARM’ and Section 5 ‘WHERE 

NOT TO PUT THE ALARM’).
The model number and supply voltage are marked on the power 

supply unit and can be viewed with the outer cover removed.

Models SF340E, SF340F, SF340J

1.  Remove the outer cover of the unit by gently pushing in the 2  

  edge clips. Remove the power supply unit by pushing in the   

  lower clip and lifting off.
2.  Decide where the electrical supply cable is to enter the unit and  

  cut out the appropriate cable entry on the base. If the wiring to  

  the unit is surface mounted, standard 16mm x 25mm electrical  

  trunking must be used for the cable.

3.  The unit has been designed to be either surface or flush  

 

  mounted:
  a) Surface Mount 

  Mark the position of the 2 mounting holes, drill two 5mm  

  diameter holes and secure the unit to the wall using the screws  

  and wall plugs provided.
  b) Flush Mount 

  Using a standard 2 gang 28mm mounting box, complete the  

  electrical connections (see below), re-fit the power supply cover  

  and secure using the 2 M3.5 screws provided.

B. Electrical Connections

Model SF340E

1. The SF340E must be supplied from a non-switched 3 Amp 

  fused spur (230Vac).
2.  Connect the supply wiring to the 3 way terminal block 

  provided. (Maximum wire size is 2.5mm²)

3.  Connect the brown wire of the power supply unit to the red or  

  brown wire of the supply (live).
4. Connect the blue wire of the power supply unit to the black 

  or blue wire of the supply (neutral).
5.  No connection must be made to the mains supply earth. 

  The earth wire can be sleeved and connected to the third    

  terminal of the block to avoid contact with any other wires.
6. Once all electrical connections are made, locate the terminal   

  block in the base by fitting on the pegs.

7.  Fit the power supply unit to the base ensuring that the  wires sit  

  in the base and do not get trapped. Check that the power  

  supply is positioned correctly and the fixing clip has operated.  

  Secure the power supply in place by tightening the securing 

  screw.

Important: The power supply securing screw must be tight-

ened to ensure electrical safety.

Model SF340F

1.  The SF340F must be supplie  

  from a nonswitched 230Vac  

  spur. No external fuse is required  

  since a fuse is incorporated in  

  the unit. (Maximum wire size is  

  2.5mm²)
2.  Connect the red or brown (live)  

  wire of the supply to the terminal  

  marked L on the connection  

  board fitted to the base of the unit.

3.  Connect the black or blue (neutral) wire of the supply to the    

  terminal marked N.
4. No connection must be made to the mains supply earth.
(Refer to later section for Relay and Interconnect Connections)

Important: The power supply securing screw must 

be tightened to ensure electrical safety.

Model SF340J

1.  The SF340J must be supplied  

 

  from a 12Vdc or 24Vdc  

  supply. No external fuse is  

 

  required since a fuse is  

  incorporated in the unit.
2. Connect the positive supply wire    

     (+12Vdc or +24Vdc) to the  

  appropriate terminal marked on    

  the base of the unit.
3.  Connect the negative supply wire (0V) to the terminal marked 0V.
4.  No connection must be made to the supply earth.
(Refer to following section for Relay and Interconnect Connections)

RELAY CONNECTIONS (Models SF340F & SF340J only)

The relay connections are made using the terminal block on the 

connection board marked RELAY O/P. Connections to the relay 

volt free contacts are as follows:
 

N/C

  

–  

Normally closed 

 

COM

  

–  

Common 

 

N/O 

 

–  

Normally open

The relay contacts are rated at 

3 Amps / 230Vac.

INTERCONNECT CONNECTIONS (Models SF340F & SF340J only)

The interconnect system is made using the terminal block on the 

connection board marked INTERCONNECT. Units are connected 

in series as follows,

  I/C

 -   Connect to I/C terminals of other SF340F or SF340J alarms

  I/C 0V

 - Connect to I/C 0V terminals of other SF340F or  

 

                SF340J alarms
A maximum of 20 units can be interconnected.

Interconnect

Relay Output

Power Input

Fuse

500mA

250V

Interconnect

Relay Output

Power Input

Fuse

500mA

250V

Alarm 1

Alarm 2

Alarm 3

Once all electrical connections have been made, fit the power 

supply unit to the base.

Ensure that the power supply clip fits correctly and then tighten 

the securing screw.

Important: The power supply securing screw must be  

tightened to ensure electrical safety.

C. Fitting the Module and Turning On

All SF340 models

The sensor module SF340M is used for all the SF340 series units. 

Simply fit the Module to the installed base and power supply unit 

and gently push down until it clips into place. The red alarm light will 

illuminate for approximately 10 seconds when the module is fitted.
NOTE: The Module must have the backup battery fitted for the alarm 

to operate correctly. This applies even if the primary power supply 

is present (230Vac, 12Vdc or 24Vdc as appropriate). If no battery is 

fitted or the battery is flat the audible alarm will sound continuously 

when the unit is installed and the primary power source is switched 

on.
Fit the outer cover of the unit by pushing until the clips at either end 

hold the cover in place.
Turn on the electrical supply. Check that the green power light  

illuminates and the red alarm lamp flashes briefly once every minute. 

Push the test button and hold until the audible alarm signal is given. 

The unit is now ready and working.

9. HOW DO I REPLACE THE SENSOR MODULE?

All SF340 models

Remove the outer cover of the unit by gently pushing in the clips 

at either end. Remove the module fixing screw (if fitted) and unclip 

the Module from the installed base and power supply unit. The 

replacement Module can simply be clipped into the power supply 

unit and the fixing screw replaced if used.
NOTE: The Module must have the backup battery fitted for the 

alarm to operate correctly. This applies even if the primary power 

supply is present (230Vac, 12Vdc or 24Vdc as appropriate). If no 

battery is fitted or the battery is flat the audible alarm will sound 

continuously when the Module is fitted.

Push the test button and hold until the audible alarm signal is 

given and the red light flashes. The unit is now ready and working.

10. BATTERIES

Only the following batteries are suitable replacements for the 

SF340M backup battery:
Duracell MN1604  

Rayovac A1604  

Gold Peak 1604A  

Energizer 6LR61/522
To replace the backup battery, remove the Module from the unit 

(see section 9), unclip the battery and replace with a fresh battery. 

Refit the Module and outer cover to the unit and push and hold 

the test button until the audible alarm signal is given and the red 

light flashes.

11. WHAT SHOULD I DO IF MY ALARM SOUNDS?

If your alarm sounds, please proceed as follows:

3

   Open all doors and windows to ventilate the area and allow the 

 

Carbon Monoxide to disperse.

Where possible turn off all fuelled appliances and stop using  

 

them.

Evacuate the property leaving the doors and windows open.

3

  Ring the gas or other fuel supplier on their emergency number  

 

and explain the problem. Keep their number in a prominent   

 

place.

3

  Do not re-enter the property until the alarm has stopped.

3

  Get medical help immediately for anyone suffering from the   

 

effects of Carbon Monoxide poisoning such as, headache,    

 

nausea etc and advise that Carbon Monoxide poisoning  

 

 

is suspected.

3

  Do not use the appliances again until they have been checked  

 

by an expert and the fault located and cleared. In the case of  

 

gas appliances this should be a CORGI registered installer.

Power Supply Scuring Screw

Backup Battery

Power Supply Unit

Issue 4/ A02894 
2102M0658
MAN0820_EMEAI
07-08
© 2008 Honeywell Analytics

Honeywell Analytics

4 Stinsford Road

Nuffield Industrial Estate

Poole BH17 0RZ
UK 
Freephone: (+44) (0) 800 0642999

Reviews: