SWIFT® Smart Wireless Integrated Fire Technology Manual —
P/N LS10036-000SK-E:G 4/13/2020
13
Mounting and Wiring
WSK-WGI Wireless System Gateway
2.7.2 Wiring
•
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction.
•
12-18 AWG is recommended.
For wiring connections:
1.
Strip about 3/8” of insulation from the end of the wire.
2.
Slide the stripped end of the wire under the appropriate terminal and tighten the screw.
Figure 2.4 Attaching Cover to Mounting Plate
2.3
.w
m
f
locating pin
locating pin
locating pin
NOTE:
Do not loop the wire under the screw terminals.
Figure 2.5 WSK-WGI Mounting Plate - Terminal Layout
A7 - SLC Out+/In+
A6 - SLC In+/Out +
A5 - SLC- (Common)
A4 - SLC Power Select 2
A3 - Power +24VDC
A2 - Power Ground
A1 - SLC Power Select 1
2.
4.w
m
f