SWIFT® Smart Wireless Integrated Fire Technology Manual —
P/N LS10036-000SK-E:G 4/13/2020
23
Operations
WSK-WGI Wireless System Gateway
4.
Perform a link test between each of the four device locations (Mesh 1 to Mesh 5, Mesh 2 to Mesh 5, Mesh 3 to Mesh 5, and Mesh 4
to Mesh 5) using a separate pair of test devices. Refer to Appendix B, “Site Survey” for instructions on how to perform a site
survey. Use SWIFT Tools to identify the signal strength/link quality for each of the four link tests and record these values.
5.
Use network statistics from the gateway to determine link strength between edge devices in each mesh.
Figure 2.21 Perform a Link Test with the Fifth Mesh
Mesh #1
Mesh #2
Mesh #5
Mesh #4
Mesh #3
Figure 2.22 Perform Link Test within Each Mesh
Mesh #1
Mesh #2
Mesh #5
Mesh #4
Mesh #3