30
SWIFT® Smart Wireless Integrated Fire Technology Manual —
P/N LS10036-000SK-E:G 4/13/2020
Section 3: Wireless Devices
3.1 Description
The SWIFT Network consists of the following devices:
WSK-PHOTO - Wireless Photoelectric Smoke Detector
FCC ID: AUBWFSSD
The wireless photoelectric smoke detector is powered by four CR123A batteries. It has a sensor head to detect smoke and LEDs to indi-
cate the activation and trouble status.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Det:Photo
WSK-PHOTO-T - Wireless Photo/Heat Detector
FCC ID: AUBWFSSD
The wireless photo/heat detector is powered by four CR123A batteries. It has a sensor head to detect heat and LEDs to indicate activa-
tion and trouble status.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Det: Photo-Heat
WSK-HEAT-ROR - Wireless Rate of Rise Heat Detector
FCC ID: AUBWFSSD
The rate of rise heat detectors are powered by four CR123A batteries. The detectors have LEDs to indicate the activation and trouble sta-
tus.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Det: Heat
WSK-HEAT - Wireless 135° Fixed Heat Detector
FCC ID: AUBWFSSD
The fixed heat detectors are powered by four CR123A batteries. The detectors have LEDs to indicate the activation and trouble status.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Det: Heat
WSK-MONITOR - Wireless Addressable Monitor Module
FCC ID: AUBWFSMM
The wireless monitor module is powered by four CR123A batteries. It can be connected to a switch within three feet of its location or
wired directly to the pull station. The module has LEDs to indicate the activation and trouble status.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Switch - Manual Pull
WSK-RELAY - Wireless Addressable Relay Module
FCC ID: AUBWFSRM
The wireless relay module is powered by four CR123A batteries
.
It provides the system with a dry-contact output for activating a variety
of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually
or through panel programming, on a select basis. The module has an LED to indicate the activation and trouble status.
Base address set by the code wheels on the sync module will use:
•
Type Code: Wireless Relay - Output
WSK-PULL-DA - Wireless Addressable Pull Station
FCC ID: AUBWFSPS
The wireless pull station is powered by four CR123A batteries. The module has an LED to indicate the activation and trouble status.
The pull station will occupy one module address.
•
Type Code: Wireless Switch - Manual Pull
SWIFT Wireless Addressable AV bases
FCC ID: AUBWFSAV
The wireless AV base is powered by eight CR123A batteries. Four of the CR123A batteries are used to power the notification element
and four of the CR123A batteries are used to power the radio communication element. The module has an LED to indicate the activation
and trouble status. The module requires a non-compact wall or ceiling System Sensor L-series notification device (ordered separately). A
notification device with an audible component must be set to a non-coded setting (i.e. continuous or Temp3). Each AV Device requires
two (2) consecutive SLC addresses on the fire panel. Use the rotary code wheels on the AV device to set the base address. The AV
Device will also occupy the address following the base address. (Base +1)
The base address on the AV base will require the following configuration:
•
Type Code: Wireless Relay - Output
Base+1 address will use the following configuration:
•
Type Code: NAC Module - Output Point
Wireless related trouble events described in Section 3.6.3 will be indicated at the base address. Open circuit at the base+1 address will
indicate a missing notification device. Short circuit at the base+1 address will indicate a incorrectly configured or faulted notification
device.