48
SWIFT® Smart Wireless Integrated Fire Technology Manual —
P/N LS10036-000SK-E:G 4/13/2020
Site Survey
Conduct a Site Survey
B.1.3 Retrieving Site Survey Results
To retrieve the site survey results:
1.
Return the device to “Pending Site Survey” or “Factory Default” mode. This is done by tampering devices that have completed a
link quality test or by rebooting devices that have completed an RF scan test.
2.
Plug the W-USB adapter into the laptop/PC where SWIFT Tools has been installed.
3.
Bring the devices within a range of approximately 20 feet from the W-USB adapter connected to the laptop/PC.
4.
Log into SWIFT Tools and retrieve the data.
!
CAUTION: SITE SURVEY RESULTS WILL BE REPLACED
DO NOT CLEAR THE TAMPER ON A DEVICE THAT IS IN THE “PENDING SITE SURVEY” STATE OR THE EXISTING
RESULTS WILL BE REPLACED.