background image

PHOTOCELL

ENABLED

MOVEMENT DETECTOR

AUTOMATIC
OPERATION

MOVEMENT

DETECTOR

SEMI-AUTOMATIC

OPERATION

NOT

USED

POWER UP

ON

POWERUP

OFF

PHOTOCELL

DISABLED

min

ON

OFF

10 

min

20 

min

OFF DELAY

Add together to give required time.

All OFF = 10 secs

(Switched-live R1) 

PHOTOCELL 

MODE 

= ACTIVE

24 Hr Cycle

*

No 24 Hr Cycle

PHOTOCELL 

MODE 

= PASSIVE

NOT

USED

Off Delay

The Off Delay may be set between 5 and 35 minutes. A 10-second Off Delay is available for walk-testing the 
product. In a typical office environment a 20-minute Off Delay is usually satisfactory.

Movement Detector Operation (Automatic / Semi-Automatic)

Where  absence  detection  is  required  (ie  the  user  manually  turns  lights  ON  if  required  but  lights  still  turn  off 
automatically once an area is vacated), semi-automatic operation can be set via the programmer.   It should be 
noted that this mode of operation affects only the switched-live output. Where semi-automatic operation is required 
on both outputs, please contact Ex-Or for assistance.

Power Up Setting (On/Off)

Set to ON the detector will automatically switch its outputs on when Mains is applied. If set to OFF, the detector will 
power up without turning its outputs on, wait for 30 seconds and THEN look for movement. Only if the area is 
occupied will the output switch on at this time. The detector must be set to Power Up ON when used in conjunction 
with semi-automatic operation.

Photocell Operation (Passive/Active/Disabled)

Both the single-output detector and the dual-output detector have an in-built photocell. On the dual-output detector 
the photocell does not affect the volt-free output - ie the volt-free output will turn ON regardless of natural light levels 
when occupancy is detected. The photocell has three modes of operation - Passive, Active and Disabled. Its 
operational  behaviour  is  governed  by  the  setting  chosen  and  by  the  values  stored  in  the  Upper  and  Lower 
thresholds (see diagram overleaf).

Passive

 - The photocell will inhibit turn-on of the controlled load if sufficient natural light is available. It will not turn 

the load off whilst an area is occupied

Active

 - The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a 

period of occupancy. This mode of operation operates in conjunction with a passing cloud timer (PCT). The PCT is 
asymmetrical in operation - the load will be switched on immediately that the light level falls below the lower set 
point, however, the load switches off only if the light level exceeds the upper threshold 

continuously

 for a period 

equal to the Off Delay.

Disabled

 - The photocell has no effect.

24hr Cycle (Yes/No)

For use in ‘Washroom Mode’ only (see overleaf).  In this mode it is necessary to have a hygiene cycle (flush) if the 
area has been unoccupied for 24hrs.   Select this feature and the output will switch on for the duration of the Off 
Delay once every 24hrs if the area remains unoccupied.  Operates on R2 (if selected) on twin-ouput unit.

Please note that additional 

parameters are available 

via the HP2000 

2

1

3

4

5

6

7

8

9

10

11

12

* Operates on R2 if Twin-Output 
Unit, R1 on Single-Output Unit.
If controlling water with Single-
Output  Unit  the  photocell 
cannot be used

OFF DELAY

Add together to give required time.

All OFF = 10 secs 

(Volt-free R2)

HP10 Parameter Options for MS1201P / MS1221P

 

W4231G

Commissioning

The units are supplied with factory default settings (Power-Up On, fully Automatic operation, a 20 minute Off Delay, 
no 24hr Cycle, Photocell Disabled).   Programme using an infrared programming tool.   Please note that the full 
range of parameters is accessible via the HP2000; the HP10 and HP18 offer different/limited programming options.  

Walk-test Mode

Walk-test mode is used to check that the detector is operating as required.  The short off-delay enables the installer 
to check that lights are switching on when movements are made at the edge of the detection zone.  It is easier to 
carry out a walk-test when the photocell is not holding the lights off.
1.  Change the Off Delay to 10 seconds using the HP10 or press ‘TEST’ (HP18) or ‘Utilities/Walk Test/OK’ (HP2000).
2.  Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before 

moving and triggering the lights back on. Re-programme the desired Off Delay once testing is complete. Note: If 
the HP2000 or HP18 was used to engage ‘soft’ walk test mode as described above, the programmed Off Delay 
will be automatically restored after 5 minutes.

Summary of Contents for Silver Series

Page 1: ...nicalsales ex or honeywell com www ex or com At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with normal household waste Do not burn by Honeywell Note Infrared Programmer required for commissioning HP2000 HP10 or HP18 for MS1201PF SM HP2000 or HP10 for MS1221PF SM Please note that only the HP2000 offers the full rang...

Page 2: ... 3 Ameans for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations 4 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of some lighting types e g 2D luminaires may specify a maximum number of switching cycles and or a minimum on time in order to achieve a predicted lamp life Please che...

Page 3: ...ed load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the light level falls below the lower set point however the load switches off only if the light level exceeds the upper threshold continuousl...

Page 4: ...own momentarily on the HP2000 screen following the Download this is a useful mechanism for troubleshooting Washroom Mode The unit may be used in conjunction with a 230V solenoid valve and a trickle valve or petcock to effect a urinal flush system Set the water flow rate by adjusting the petcock so that the cistern just fills within the chosen Off Delay period of the detector Note that in this mode...

Reviews: