Setting the Photocell (Photocell only affects the ‘Live Out’ output)

1.

If  the  lights  are  not  already  on,  switch  them  on  manually  by  pressing  ‘Utilities/User  Remote/Lu/OK’ 
[HP2000], or ‘Up’ [HP10] or ‘On’ [HP18].  Fluorescent lights do not reach full output until up to 15 minutes after being 
switched on, so ensure that the lights are fully warmed up before continuing.   This stage may be omitted if the 
intention  is  to  operate  the  detector’s  photocell  in  Passive  Mode  only  [the  detector  must  have  already  been 
programmed to Passive Mode].

2.

Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to be on, and 

above which you 

would not

 want the lights to be on.

3.  Start the internal self-programming mechanism by pressing ‘Utilities/Set Light Level/OK’ [HP2000], or ‘Store’ [HP10] 

or  ‘Set’  [HP18].    The  detector  takes  a  measurement,  adds  a  small  amount  and  stores  the  value  in  the  Upper 
Threshold.   Then it turns the lights off, makes another measurement and stores the value in the Lower Threshold.   
The lights now switch on again to acknowledge a successful programming operation.

The two switching thresholds have now been set, and the difference between them is equal to the contribution made by 
the electric lighting;  this is the perfect amount of hysteresis to ensure that the lights will not oscillate.  The thresholds may 
be read back and fine-tuned if necessary using the HP2000. Please note that the values are non-specific units  i.e. not lux.

Note:

  The light level perceived by the detector at the moment immediately prior to a Download operation [HP2000 only] is 

shown momentarily on the HP2000 screen following the Download;  this is a useful mechanism for troubleshooting.

Washroom Mode

The unit may be used in conjunction with a 230V solenoid valve and a trickle valve or ‘petcock’ to effect a urinal flush 
system.  Set the water flow rate by adjusting the petcock so that the cistern 

just

 fills within the chosen Off Delay period of 

the detector.  Note that in this mode, the photocell should be disabled, unless using the dual output unit.

Note:

 The MS1201PF/PSM and MS1221PF/PSM and 230V solenoid valve can be ordered as a complete product, Ex-Or 

part nos. UC1201PF/PSM and UC1221PF/PSM.

Lights ON =

Lights OFF =

Upper Threshold

Lower Threshold

Natural
Light 
Level

Duration of 

Off Delay

Note that when the natural light 
level exceeds the ‘upper threshold’ 
value, the lights do not immediately 
turn off. They will turn off only when 
the upper threshold has been 
exceeded for the duration of the 
programmed Off Delay.

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

Technical Data

 

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
RECOMMENDED CIRCUIT PROTECTION: 10 Amps

2

TERMINAL CAPACITY: 2 x 2.5mm
MAXIMUM LOAD: 6 Amps per output [not exceeding 10A in total]
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3 metres
RANGE: Cone-shaped detection 
               pattern, diameter (at floor level)
               = 2.4 x mounting height

PHOTOCELL: Adjustable 50-5000 lux via HP2000/HP10/HP18
OFF DELAY 1 & 2:  Adjustable via Programmer - factory pre-set to 20 mins

Options: 1 min - 96 hours / Disabled via HP2000; 5-35 mins via HP10 (also 5, 10 or 20 mins via HP18 - 
MS1201PF/SM only) plus 10-second Walk-test Mode
On MS1221PF/SM each output is independently adjustable (via HP2000 or HP10)

COLOUR: White
MATERIAL: Flame retardant PC/ABS
WEIGHT:  200g approx
IP RATING: 3X

Dimensions

100mm

10mm deep

(Flange)

62mm

deep

(behind ceiling)

6.0m

2.5m

Summary of Contents for Silver Series

Page 1: ...nicalsales ex or honeywell com www ex or com At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with normal household waste Do not burn by Honeywell Note Infrared Programmer required for commissioning HP2000 HP10 or HP18 for MS1201PF SM HP2000 or HP10 for MS1221PF SM Please note that only the HP2000 offers the full rang...

Page 2: ... 3 Ameans for disconnection must be incorporated in the fixed wiring in accordance with the current wiring regulations 4 This equipment switches lights no more frequently than would a responsible human occupant However manufacturers of some lighting types e g 2D luminaires may specify a maximum number of switching cycles and or a minimum on time in order to achieve a predicted lamp life Please che...

Page 3: ...ed load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the light level falls below the lower set point however the load switches off only if the light level exceeds the upper threshold continuousl...

Page 4: ...own momentarily on the HP2000 screen following the Download this is a useful mechanism for troubleshooting Washroom Mode The unit may be used in conjunction with a 230V solenoid valve and a trickle valve or petcock to effect a urinal flush system Set the water flow rate by adjusting the petcock so that the cistern just fills within the chosen Off Delay period of the detector Note that in this mode...

Reviews: