12
32-00009—01
Complex Functions Min
Typical Max
Units
Thermocouple
T2
&
T3
Type J
Range
-200.0 -
1025.0 °C
Resolution
-
0.1
-
°C
Accuracy
-5.0
-
5.0
°C
Type K
Range
-150.0 -
1000.0 °C
Resolution
-
0.1
-
°C
Accuracy
-5.0
-
5.0
°C
RTD
T3
&
T4
PT100
Range
-135.0 -
250.0
°C
3 wire, 100 Ω
Resolution
-
0.5
-
°C
Accuracy
-2.0
-
2.0
°C
Type
PT1000
Range
-135.0 -
250.0
°C
3 wire, 1000 Ω
Resolution
0.5
°C
Accuracy
-2.0
-
2.0
°C
NTC
T3
&
T4
Type
10K
Range
-40.0
-
175.0
°C
Resolution
-
0.1
-
°C
Accuracy
a
-2.0
-
2.0
°C
-40 °C to 25 °C
-1.0
-
1.0
°C
25 °C to 125 °C
-1.5
-
1.5
%
-3.0
-
3.0
°C
-40 °C to 175 °C
a
Temperatures refer to sense range.
Table 5. Specifications Cell Complex Functions.