APPLICATION

SLATE brings configurable safety and programmable 
logic together into one single platform. The SLATE 
program can easily be customized for almost any 
application—offering virtually limitless development 
opportunities with far less complexity.

The SLATE Low Torque Actuator series includes 
commercial- and industrial-grade 1/4-turn actuators 
available in 50 and 150 in/lb models with highly 
repeatable position accuracy designed specifically to 
integrate with the SLATE system. This series is well 
suited for the precise control of air and gas flow and 
can operate in a wide range of temperatures and 
environmental conditions.

SLATE™ Low Torque Actuator can be easily mounted 
to the following valves using the mounting kits noted 
below. These kits can be ordered via 
www.customer.honeywell.com.
• Maxon CV Valve Series (1/2"–2")

mounting kit #50123928-001

• Honeywell V51E Valve Series (1-1/2"–2")

mounting kit #50124386-001 and mounting kit 
#32003396-001

• Honeywell V51E Valve Series (2-1/2"–4")

mounting kit #50124386-001 and mounting kit 
#32003396-002

• Honeywell V5197A Valve Series (3/4"–3")

mounting kit #50124386-001

FEATURES AND BENEFITS

• Offered in two different configuration options:

NEMA 1 rated, operating in a temperature 
range of -18 to 158 °F (-28 to 70 °C) with 
450 positions over a 90° span

NEMA 4 rated, operating in a temperature 
range of -40 to 158 °F (-40 to 70 °C) with 
900 positions over a 90° span

• Field-reversible clockwise and counterclockwise 

rotation operation.

• Internal temperature, valve status, health 

diagnostics, and error codes reporting.

• Robust, heavy-duty construction, continuous 

duty cycle-rated.

• Closed loop position control via Modbus RS-485 

communications as an input to the SLATE Fuel 
Air Ratio Module, part R8001C6001.

• Dual 1/2-in knockout conduit connections.

• 1/2-in keyed output shaft with a 1/8-in square 

key.

• Die-cast aluminum base with high-impact 

resistant, reinforced plastic cover.

• Meets UL353 Safety for Limit Controls.

• Meets UL1998 when used with R8001C6001 

SLATE Fuel Air Ratio Module.

APPROVALS

SLATE Commercial Model

Underwriters 
Laboratories

Meets UL353 Safety for Limit 
Controls.
Meets UL1998 when used with 
R8001C6001 SLATE Fuel Air Ratio 
Module.

CE

2009/142/EC: Gas Appliance 
Directive
(EN 12067-2:2004, EN298-2012)

Summary of Contents for SLATE Series

Page 1: ...it 32003396 001 Honeywell V51E Valve Series 2 1 2 4 mounting kit 50124386 001 and mounting kit 32003396 002 Honeywell V5197A Valve Series 3 4 3 mounting kit 50124386 001 FEATURES AND BENEFITS Offered in two different configuration options NEMA 1 rated operating in a temperature range of 18 to 158 F 28 to 70 C with 450 positions over a 90 span NEMA 4 rated operating in a temperature range of 40 to ...

Page 2: ...8001M1150 150 in lb Actuator NEMA 1 Enclosure Industrial R8001M4050 50 in lb Actuator NEMA 4 Enclosure R8001M4150 150 in lb Actuator NEMA 4 Enclosure Table 1 Model Specifications Actuator Options Specs Commercial Model Industrial Model 50 in lb R8001M1050 150 in lb R8001M1150 50 in lb R8001M4050 150 in lb R8001M4150 Communication RS 485 non isolated RS 485 non isolated RS 485 Isolated RS 485 Isola...

Page 3: ...tor has been independently evaluated by Underwriters Laboratories to provide position feedback to the SLATE Fuel Air Ratio Module The safety of the overall system is ultimately the responsibility of 1 The upstream safety control that commands and monitors the SLATE Actuator and 2 the trained commissioning engineer that configures the unit for system operation WARNING Safety Hazard Before operating...

Page 4: ...or first ensuring exact alignment After the coupling is tightened assemble and tighten the mounting brackets Do not tighten the mounting brackets first 6 Observe the actuator while it travels over its entire range and ensure smooth operation If sticking binding is observed or if Slate reports actuator error codes the actuator shaft is not properly aligned and must be re adjusted Ensure the media t...

Page 5: ...d by the application Use a gauge of wire to minimize voltage loss droop over long cable runs especially at full current load Ensure that voltage specifications are met under all conditions See Table 2 A fuse or breaker should be installed at the power source If the power supply is not factory supplied a SELV Safety Extra Low Voltage rated supply with regulated output must be provided Communication...

Page 6: ...ctuators Use a slow blow fuse if additional external fusing is desired Required gauges are Up to 80 ft 24 AWG Up to 120 ft 22 AWG Up to 500 ft 16 AWG Up to 800 ft 14 AWG Up to 1200 ft 12 AWG 24V 24VDC negative terminal Low voltage communication Modbus over RS 485 Industrial models only R8001M4050 R8001M4150 RS485 In Isolated RS 485 positive Shielded twisted pair cable with a separate common wire i...

Page 7: ...ignment and make necessary adjustments Alarm and lockout event reporting SLATE alarm and lockout codes are accessed through the SLATE Fuel Air Ratio Module or using the SLATE touchscreen display See documents 32 00013 and 32 00006 for more information The Low Torque Actuators also display status messages through LED blinks The LED is on the PCB inside the unit These can be used for troubleshooting...

Page 8: ...Safety data corruption 6 Stack Overflow Program execution error 7 System Tick Program execution error 8 Main Loop Program execution error 9 Processor Fault Instruction test failure 10 Processor Fault Memory RAM ROM failure 叛屛齟 Component Name 繢橲銘 Hazardous Substances Pb Lead Pb 蟍 Hg Mercury Hg Cd Cadmium Cd 堘叝 Cr6 Chromium VI Compounds Cr6 撲譾 PBB Polybromin ated Biphenyls PBB 撲譾匱 PBDE Polybromin at...