42
Parameters
Honeywell
8
8.9 PROTECTIONS (CONTROL PANEL: MENU PAR -> P9)
NOTE!
These parameters are shown, when
P13.1 = 0
.
8.10 AUTORESTART PARAMETERS (CONTROL PANEL: MENU PAR ->
P10)
NOTE!
These parameters are shown, when
P13.1 = 0
.
Code
Parameter
Min
Max
Unit Default ID
Note
P9.1
Response to 4mA
reference fault
0
2
1
700
0
= No response
1
= Warning
2
= Fault, stop acc. to
P2.3
P9.2
Response to under
voltage fault
0
2
2
727
P9.3
Earth fault protection
0
2
2
703
P9.4
Stall protection
0
2
1
709
P9.5
Underload protection
0
2
0
713
P9.6
Reserved
P9.7
Thermal protection of
the motor
0
2
2
704
P9.8
-20
100
C
40
705
P9.9
Motor cooling factor
at zero speed
0,0 150,0
%
40,0
706
P9.10
1
200
min
45
707
P9.11
Motor Phase
Supervision
0
2
unit
2
702
0
= No response
1
= Warning
2
= Fault, stop mode after
fault according to P2.3
Table 8.9: Protections
Code
Parameter
Min
Max
Unit
Default
ID
Note
P10.1 Wait time
0,10 10,00
s
0,50
717
Delay before automatic restart
after a fault has disappeared
P10.2 Trial time
0,00 60,00
s
30,00
718
Defines the time before the
inverter tries to automatically
restart the motor after the fault
has disappeared
P10.3 Start function
0
2
0
719
0
= Ramp
1
= Flying start
2
= According to P4.2
P10.4
Automatic
restart
0
1
0
731
0
= Disabled
1
= Enabled
Table 8.10: Autorestart parameters