0.
4.2. STUW751 Terminal Connections
Revision 1
SmartLine Wireless Temperature and Universal I/O User's Manual
33
4.2 STUW751 Terminal Connections
HLAI (0/4-20mA) or T/C or mV or DI or 2 Wire Resistance
AND Digital Output
1
2
3
4
5
6
TB1
TB2
PV1
PV2
+
+
-
-
+
-
+
-
+
-
PV3 Digital
Output
Figure 4-3: STUW751 Terminal Connections
NOTES:
1. The terminals accept 14-26AWG wire, and the screws shall be torqued to 0.4-0.5Nm (3.5 – 4.4
in-lb)
2. Any combination of sensor type inputs is allowed
3. Shielded cable is required for EMC conformity and is recommended for all remote sensor
installations. The shield shall be grounded at the transmitter end only. If the shield is grounded at
the remote end, the shield shall not be connected at the transmitter end.
4. When remote mounted probe sensors are used and the shield is grounded at the probe, the
shield shall not be connected at the transmitter end.
5. Duplex (redundant) sensors that are bonded to the probe are not permitted. All
thermocouple/mV, RTD/ohms, and HLAI inputs must be isolated from ground (the probe) and
from each other.
6. Digital Input switches, DI, must be dry contact type, simple apparatus and properly segregated
from all other sources of power.
Summary of Contents for SmartLine STIW400
Page 93: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 81 ...
Page 94: ...82 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 95: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 83 ...
Page 96: ...84 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 97: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 85 ...
Page 98: ...86 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 99: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 87 ...
Page 100: ...88 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 101: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 89 ...