7. Operation
7.2. Transmitter PV display
48
SmartLine Wireless Temperature and Universal I/O User's Manual
Revision 1
Transmitter display
OneWireless User
Interface display
Definition
What to do
‘U’ Status
Excess Span
Calibration
The calibrated upper
and lower trim has
produced a span that is
greater than 5% of the
characterized span of
the transmitter.
Clear Calibration
Or
Set Factory Calibration
Or
Check the applied trim points
and re-attempt lower and
upper (trim) calibration.
‘U’ Status
Excess Calibrated
Range
The selected
calibration points used
for upper and lower
trim are outside the
characterized range of
the transmitter.
Check that the upper and
lower trim points are both
within the characterized range
of the transmitter and re-
attempt upper and lower (trim)
calibration.
blank
Calibration Cleared
Indicates that both the
upper and lower trim
points as well as the
zero offset has been
cleared. The calibration
source is none.
Calibration the zero offset
Or
Calibrate using the lower and
upper trim points.
Summary of Contents for SmartLine STIW400
Page 93: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 81 ...
Page 94: ...82 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 95: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 83 ...
Page 96: ...84 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 97: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 85 ...
Page 98: ...86 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 99: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 87 ...
Page 100: ...88 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 101: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 89 ...