Revision 1
SmartLine Wireless Temperature and Universal I/O User's Manual
71
Name
Description
Data Ty D Access
Class
Enum Value
Enum Description
CAL_CMD
Calibration command
Uint8 1 Read/Write Dynamic
0 - None
No value
1 - Cal Lower
Calibrate for lower value
2 - Cal Upper
Calibrate for upper value
3 - Cal Restore
Restore calibration
4 - Cal Clear
Clear calibration
CAL_STATUS
Calibration status
Uint8 1 Read Only Dynamic
0 - None
No value
1 - Success
Calibration successful
2 - Failed
Calibrate failed
3 - Bad Factory Cal
Bad factory calibration
4 - Bad User Cal
Bad user calibration
5 - Internal Error
Internal error
6 - Bad Units
Bad units
7 - Bad Sensor
Bad sensor
8 - Bad Trim Point
Bad trim point
9 - Success with Excess Success with Excess
CAL_POINT_HI Cal Point High
Float 4 Read/Write Static
CAL_POINT_LO Cal point low
Float 4 Read/Write Static
CAL_SOURCE
Calibration Source
Uint8 1 Read Only Dynamic
1 - None
Calibration source none
2 - User
User Calibration
3 - Factory
Factory Calibration
CAL_UNIT
Units of calibration point
Uint16 2 Read/Write Static
1001 - A°C
degree Celsius
1002 - A°F
degree Fahrenheit
1243 - mV
millivolt
1342 - %
percent
SENSOR_TYPE Describes the type of sensor. Different values for different types of AITB (Thermocouple, mV, mA, Ohm, RTD, etc)
Uint8 1 Read/Write Static
ThermoCouple AITB
1 - TC-B
Thermocouple B type
2 - TC-E
Thermocouple E type
3 - TC-J
Thermocouple J type
4 - TC-K
Thermocouple K type
5 - TC-NIC
Thermocouple NIC type
6 - TC-R
Thermocouple R type
7 - TC-S
Thermocouple S type
8 - TC-T
Thermocouple T type
RTD AITB
1 - PT100
PT100 RTD Type
2 - PT200
PT200 RTD Type
3 - PT500
PT500 RTD Type
Current AITB
1 - 0 - 20 mA
Zero To Twenty Milliamp Range
2 - 4 - 20mA
Four To Twenty Milliamp Range
Millivolt AITB
1 - 0 - 10 mV
Zero to Ten Millivolt Range
2 - 0- 50 mV
Zero to Fifty Millivolt Range
3 - 0- 100 mV
Zero to One Hundred Millivolt Range
Resistance AITB
1 - 0 - 100 Ohms
Zero to One Hundred Ohm Range
2 - 0- 200 Ohms
Zero to Two Hundred Ohm Range
3 - 0- 500 Ohms
Zero to Five Hundred Ohm Range
3 - 0- 1000 Ohms
Zero to One Thousand Ohm Range
PV.STATUS
The Status of the Process Variable
1 Read
Dynamic
The Status of the Process Variable
COLD_JUNC
The Value of the Cold Junction Sensor
float
4 Read
Dynamic
Only Available on Thermocouple type AITBs
Table A-3: AITB Modbus Table
Summary of Contents for SmartLine STIW400
Page 93: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 81 ...
Page 94: ...82 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 95: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 83 ...
Page 96: ...84 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 97: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 85 ...
Page 98: ...86 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 99: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 87 ...
Page 100: ...88 SmartLine Wireless Temperature and Universal I O User s Manual Revision 1 ...
Page 101: ...Revision 1 SmartLine Wireless Temperature and Universal I O User s Manual 89 ...