background image

SV9510/SV9520 SMARTVALVE™ SYSTEM CONTROLS

69-2014

10

LP, at the tank. Also shut off gas supply before 
disconnecting manometer and replacing plug. Repeat 
Gas Leak Test at plug with main burner operating.

NOTE: Check the inlet pressure before adjusting the 

pressure regulator.

1.

Check the full rate manifold pressure listed on the 
appliance nameplate. Ignition system control full 
rate outlet pressure should match this rating.

2.

With main burner operating, check the ignition 
system control flow rate using the meter clocking 
method or check pressure using a manometer 
connected to the outlet pressure tap on the ignition 
system control. See Fig. 4.

3.

If necessary, adjust the pressure regulator to match 
the appliance rating. See Tables 7 and 8 for factory-
set nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise 

to increase or 

counterclockwise 

   to decrease the gas 

pressure to the burner.

c. Always replace the cap screw and tighten firmly 

to prevent gas leakage.

4.

If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the ignition system control, 
check the ignition system control inlet pressure 
using a manometer at the ignition system control 
inlet pressure tap. If the inlet pressure is in the 
nominal range (see Tables 8A and 8B), replace the 
ignition system control. Otherwise, take the 
necessary steps to provide proper gas pressure to 
the control.

NOTE: If the burner firing rate is above the capacity (at 1 

in. wc pressure drop) of the control (see Table 3 
for capacities), it may not be possible to deliver 
the desired outlet pressure. This is an application 
issue, not a control failure. Take whatever steps 
are required to correct the situation.

5.

STEP-OPENING PRESSURE REGULATORS 
ONLY. Carefully check the burner lightoff at step 
pressure. Make sure the burner lights smoothly and 
without flashback to the orifice. Make sure all ports 
remain lit. Cycle the burner several times, allowing 
at least 60 seconds between cycles for the 
regulator to resume the step function. Repeat after 
allowing the burner to cool. Readjust the full rate 
outlet pressure, if necessary, to improve lightoff 
characteristics.

Table 7. Pressure Regulator Specification Pressures (in. wc).

Table 8. Pressure Regulator Specification Pressures (kPa).

MAINTENANCE

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property 
damage.

Do not attempt to take the control apart or clean it. 
Improper cleaning or reassembly can cause gas 
leakage.

Regular preventive maintenance is important in 
applications such as in the commercial cooking and 
agricultural and industrial industries that place a heavy 
load on system controls because:

• In many such applications, particularly commercial 

cooking, the equipment operates 100,000 to 200,000 
cycles per year. Such heavy cycling can wear out the 
gas control in one to two years.

• Exposure to water, dirt, chemicals and heat can 

damage the gas control and shut down the control 
system.

The maintenance program should include regular 
checkout of the control as outlined in the Startup and 
Checkout section, and the control system as described in 
the appliance manufacturer literature.

Maintenance frequency must be determined individually 
for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 200,000 

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally 

should be checked before shutdown and again before 
the next use.

• Consequence of unexpected shutdown. Where the 

cost of an unexpected shutdown would be high, the 
system should be checked more often.

• Dusty, wet, or corrosive environment. Since these 

environments can cause the gas control to deteriorate 
more rapidly, the system should be checked more often.

The system should be replaced if:
• It does not perform properly on checkout or 

troubleshooting.

• The gas control is likely to have operated for more than 

200,000 cycles.

• The control is wet or looks as if it has been wet.

Model Type

Type of 

Gas

Nominal Inlet 

Pressure Range

Factory Set Nominal Outlet 

Pressure

Setting Range

Step

Full Rate

Step

Full Rate

Standard, Slow

NAT

5.0-7.0

3.5

3.0-5.0

LP

12.0-14.0

10.0

8.0-12.0

Model Type

Type of 

Gas

Nominal Inlet 

Pressure Range

Factory Set Nominal Outlet 

Pressure

Setting Range

Step

Full Rate

Step

Full Rate

Standard, Slow

NAT

1.2-1.7

0.9

0.7-1.2

LP

2.9-3.9

2.5

2.0-3.0

Summary of Contents for SmartValve SV9510

Page 1: ...table for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ranges and regulator types Line voltage polarity sensing models monitor the l...

Page 2: ...minal in the SV9510 SV9520 wiring harness This can burn out the heat anticipator in the thermostat or damage the system transformer IMPORTANT Ignition system controls with step opening regulators SV9510P SV9520P CANNOT be field converted to LP or natural gas Pipe Adapters Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 8 Flange kits include one flange with attached O ri...

Page 3: ...tmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control...

Page 4: ...part number 396021 to convert from natural manufactured to LP gas order part number 396025 to convert from LP to natural manufactured gas IMPORTANT Ignition system controls with step opening regulators SV9510P SV9520P CANNOT be field converted to LP or natural gas Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose the appropriate flang...

Page 5: ... the pipe is inserted too deeply Table 6 NPT Pipe Thread Length in 4 Apply a moderate amount of good quality pipe compound do not use Teflon tape only to the pipe leaving two end threads bare On LP installations use a compound resistant to LP gas See Fig 3 Fig 3 Use moderate amount of pipe compound 5 Remove the seals over the ignition system control inlet and outlet if necessary 6 Connect the pipe...

Page 6: ... larger An appliance system power review is recommended Install a transformer thermostat and other controls as required 2 Connect the 120 Vac power supply HOT lead to L1 on the ST9160 or 208907 Terminal Board 3 Appliance chassis must have reliable connection to earth ground 4 Connect control circuit to the ignition system control using the keyed connector See Fig 7 through 10 Ground Commonality Ch...

Page 7: ...ER AIR DATA NEUTRAL 2 1 3 ELECTRONIC AIR CLEANER CIRCULATING FAN HUMIDIFIER L2 L1 HOT TO 120 VAC 60 HZ POWER SUPPLY THERMOSTAT R R C W Y Y G G ST9160 ELECTRONIC FAN TIMER HOT SURFACE IGNITER FLAME ROD L1 1 1 5 6 7 8 1 2 2 2 1 3 5 4 6 2 3 3 3 4 4 4 40 VA TRANSFORMER P1 C1 C2 C3 40 VA TRANSFORMER L1 L1 L2 24 VAC R W C COM XFMR XFMR LOAD COMMON M12175E AIR PROVING SWITCH NEUTRAL NEUTRAL HOT ROLL OUT ...

Page 8: ...PROPER SYSTEM OPERATION APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND IN THIS APPLICATION POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT 1 2 3 4 5 5 CIRCULATOR R C G Y W 1 3 4 6 L2 L1 HOT 1 2 3 TO 120 VAC 60 HZ POWER SUPPLY C1 C2 C3 AIR PROVING SWITCH AQUASTAT CONTROL NEUTRAL HOT ROLL OUT SWITCH LIMIT SWITCH COMBUSTION AIR BLOWER AIR SV9410 ...

Page 9: ...cannot be stopped Check and Adjust Gas Input and Burner Ignition CAUTION Equipment Damage Hazard Exceeding input ratings can damage the controls Do not exceed input rating stamped on appliance nameplate or manufacturer s recommended burner orifice pressure for size orifice s used Make certain primary air supply to main burner is properly adjusted for complete combustion Follow instructions of appl...

Page 10: ...wing the burner to cool Readjust the full rate outlet pressure if necessary to improve lightoff characteristics Table 7 Pressure Regulator Specification Pressures in wc Table 8 Pressure Regulator Specification Pressures kPa MAINTENANCE WARNING Fire or Explosion Hazard Can cause severe injury death or property damage Do not attempt to take the control apart or clean it Improper cleaning or reassemb...

Page 11: ...ntil appliance lights or an abnormal or unexpected event is observed See next section Troubleshooting Without LED Indicator Assistance Appliance power or thermostat call for heat has cycled since appliance failure occurred WARNING Electrical Shock Hazard Can cause severe injury death or property damage Only a trained experienced service technician should perform this troubleshooting 1 Make sure th...

Page 12: ...e If you do not smell gas continue with the next step 6 Move the ignition system control switch to the ON position 7 Replace the ignition system control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on move the ignition system control switch to the OFF position and contact a qualified service technician fo...

Page 13: ...H PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE CLOSES YES YES ...

Page 14: ...ll for heat is still present 1 Gas supply off or at too low pressure to operate appliance 2 Damaged or broken HSI element 3 Line voltage HOT leadwire not connected to L terminal on ST9160 or Terminal Board 4 Appliance not properly earth grounded 5 Flame sense rod contaminated or in incorrect location 6 HSI element located in incorrect position 7 Hot surface element or flame sense rod wiring in goo...

Page 15: ...e air intake or exhaust flue system that prevent proper combustion air flow Prepurge time has expired HSI element does not glow red within 10 to 15 seconds 1 Broken or damaged HSI element 2 Broken or damaged HSI element leadwires 3 SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 failure to power HSI element HSI element is glowing red No other visible control system action Wait for HSI element warmup tim...

Page 16: ...pplication Universal Service Part Gas Type Opening Characteristics Ambient Temperatur e Range Includes Replaces Natural to LP Conversion Kit 3 4 in x 1 2 in Reducer Bushings Extension Harness Direct Ignition SV950M2511 Natural Standard Opening 40 F to 175 F 40 C to 79 C Yes None No SV9510M2347 SV9510M2362 SV9410M2902 SV9510M2412 SV9510M2354 SV9410M2910 SV9510M2388 SV9510M2420 SV9520M2536 SV9420M23...

Reviews: