background image

SV9510/SV9520 SMARTVALVE™ SYSTEM CONTROLS

9

69-2014

Fig. 10. SV9510/SV9520 typical wiring connections 

direct to the system thermostat.

STARTUP AND CHECKOUT

Ignition System Control Switch Settings

Ignition system control switch settings are as follows:

OFF prevents main gas flow through the ignition 
system control.

ON permits gas to flow through the control body. At the 
appropriate time in the appliance operation, main gas 
can flow to the main burner.

NOTE: Controls are shipped with the ignition system 

control switch in the ON position. If the appliance 
is operated with the ignition system control 
switch in the OFF position, the system will 
respond as if the air proving switch is stuck in the 
no airflow position.

Turn on Main Burner

Follow the instructions provided by the appliance 
manufacturer or turn up the thermostat to call for heat.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury or 
death.

Check for gas leaks with soap and water solution 
any time work is done on a gas system.

CAUTION

Equipment Damage Hazard.
Liquid can damage the SmartValve™ Control.

Do not spray soap and water solution on the 
SmartValve™ housing. Do not use an excessive 
amount of soap and water solution to perform the 
gas leak test. These can damage the control.

Gas Leak Test

1.

Paint pipe connections upstream of the ignition sys-
tem control with rich soap and water solution. Bub-
bles indicate a gas leak.

2.

If a leak is detected, tighten the pipe connections.

3.

Stand clear of the main burner while lighting to 
prevent injury caused from hidden leaks that could 
cause flashback in the appliance vestibule. Light 
the main burner.

4.

With the main burner in operation, paint the pipe 
joints (including adapters) and the control inlet and 
outlet with rich soap and water solution.

5.

If another leak is detected, tighten the adapter 
screws, joints, and pipe connections.

6.

Replace the part if a leak cannot be stopped.

Check and Adjust Gas Input and Burner 

Ignition

CAUTION

Equipment Damage Hazard.
Exceeding input ratings can damage the 
controls.

Do not exceed input rating stamped on appliance 
nameplate, or manufacturer’s recommended 
burner orifice pressure for size orifice(s) used. 
Make certain primary air supply to main burner is 
properly adjusted for complete combustion. Follow 
instructions of appliance manufacturer.

Checking Gas Input by Clocking Gas Meter:

Make certain there is no gas flow through the meter other 
than to the appliance being checked. Other appliances 
must remain off with the pilots extinguished (or that 
consumption must be deducted from the meter reading). 
Convert flow rate to Btuh as described in form 70-2602, 
Gas Controls Handbook, and compare to Btuh input 
rating on appliance nameplate.

Checking Gas Input with Manometer:

Make sure the ignition system control is in the OFF 
position before removing outlet pressure tap plug to 
connect manometer (pressure gauge). Also move the 
ignition system control switch to the OFF position when 
removing the gauge and replacing the plug. Before 
removing inlet pressure tap plug, shut off gas supply at 
the manual valve in the gas piping to the appliance or, for 

C1

C2

C3

LOAD

COMMON

THERMOSTAT

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.

CONNECT 120V (HOT) LEAD AS SHOWN.

APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO

EARTH GROUND.

DATA AND R LINES MUST BE CONNECTED TO W ON THERMOSTAT 

FOR PROPER SYSTEM OPERATION.

THERMOSTAT MUST HAVE ZERO OFF-STATE CURRENT DRAW. 

MECHANICAL SWITCH THERMOSTATS RECOMMENDED.  TRIAC

SWITCH THERMOSTATS OR POWER-STEALING THERMOSTATS 

ARE NOT RECOMMENDED.

IN THIS APPLICATION, POSTPURGE FUNCTION IS NOT AVAILABLE

AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT.

1

4

5

6

6

3

2

2

5

4

1

M12173E

AIR

PROVING

SWITCH

NEUTRAL
HOT

L2
L1
(HOT) 

TO

120 VAC, 60 HZ 

POWER SUPPLY

ROLL-OUT

SWITCH

LIMIT

SWITCH

COMBUSTION

AIR BLOWER

R

W

R

C

AIR

DATA

40 VA

TRANSFORMER

L1 L2

SV9410/SV9420;

SV9510/SV9520;

SV9610/SV9620

HOT 

SURFACE 

IGNITER

FLAME ROD

3

AUXILIARY

LIMIT SWITCH

(OPTIONAL)

1

1

2

5

6

7

8

1

2

2

3

3

3

4

4

4

Summary of Contents for SmartValve SV9510

Page 1: ...table for a wide range of fan assisted combustion gas fired appliances including furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ranges and regulator types Line voltage polarity sensing models monitor the l...

Page 2: ...minal in the SV9510 SV9520 wiring harness This can burn out the heat anticipator in the thermostat or damage the system transformer IMPORTANT Ignition system controls with step opening regulators SV9510P SV9520P CANNOT be field converted to LP or natural gas Pipe Adapters Angle and straight adapters available for 3 8 1 2 and 3 4 in pipe See Table 8 Flange kits include one flange with attached O ri...

Page 3: ...tmosphere make sure air circulation around the control is adequate to prevent condensation Also regularly check out the system Corrosive Chemicals Corrosive chemicals can attack the control eventually causing a failure If chemicals are used for routine cleaning avoid contact with the control Where chemicals are suspended in air as in some industrial or agricultural applications protect the control...

Page 4: ...part number 396021 to convert from natural manufactured to LP gas order part number 396025 to convert from LP to natural manufactured gas IMPORTANT Ignition system controls with step opening regulators SV9510P SV9520P CANNOT be field converted to LP or natural gas Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose the appropriate flang...

Page 5: ... the pipe is inserted too deeply Table 6 NPT Pipe Thread Length in 4 Apply a moderate amount of good quality pipe compound do not use Teflon tape only to the pipe leaving two end threads bare On LP installations use a compound resistant to LP gas See Fig 3 Fig 3 Use moderate amount of pipe compound 5 Remove the seals over the ignition system control inlet and outlet if necessary 6 Connect the pipe...

Page 6: ... larger An appliance system power review is recommended Install a transformer thermostat and other controls as required 2 Connect the 120 Vac power supply HOT lead to L1 on the ST9160 or 208907 Terminal Board 3 Appliance chassis must have reliable connection to earth ground 4 Connect control circuit to the ignition system control using the keyed connector See Fig 7 through 10 Ground Commonality Ch...

Page 7: ...ER AIR DATA NEUTRAL 2 1 3 ELECTRONIC AIR CLEANER CIRCULATING FAN HUMIDIFIER L2 L1 HOT TO 120 VAC 60 HZ POWER SUPPLY THERMOSTAT R R C W Y Y G G ST9160 ELECTRONIC FAN TIMER HOT SURFACE IGNITER FLAME ROD L1 1 1 5 6 7 8 1 2 2 2 1 3 5 4 6 2 3 3 3 4 4 4 40 VA TRANSFORMER P1 C1 C2 C3 40 VA TRANSFORMER L1 L1 L2 24 VAC R W C COM XFMR XFMR LOAD COMMON M12175E AIR PROVING SWITCH NEUTRAL NEUTRAL HOT ROLL OUT ...

Page 8: ...PROPER SYSTEM OPERATION APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND IN THIS APPLICATION POSTPURGE FUNCTION IS NOT AVAILABLE AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT 1 2 3 4 5 5 CIRCULATOR R C G Y W 1 3 4 6 L2 L1 HOT 1 2 3 TO 120 VAC 60 HZ POWER SUPPLY C1 C2 C3 AIR PROVING SWITCH AQUASTAT CONTROL NEUTRAL HOT ROLL OUT SWITCH LIMIT SWITCH COMBUSTION AIR BLOWER AIR SV9410 ...

Page 9: ...cannot be stopped Check and Adjust Gas Input and Burner Ignition CAUTION Equipment Damage Hazard Exceeding input ratings can damage the controls Do not exceed input rating stamped on appliance nameplate or manufacturer s recommended burner orifice pressure for size orifice s used Make certain primary air supply to main burner is properly adjusted for complete combustion Follow instructions of appl...

Page 10: ...wing the burner to cool Readjust the full rate outlet pressure if necessary to improve lightoff characteristics Table 7 Pressure Regulator Specification Pressures in wc Table 8 Pressure Regulator Specification Pressures kPa MAINTENANCE WARNING Fire or Explosion Hazard Can cause severe injury death or property damage Do not attempt to take the control apart or clean it Improper cleaning or reassemb...

Page 11: ...ntil appliance lights or an abnormal or unexpected event is observed See next section Troubleshooting Without LED Indicator Assistance Appliance power or thermostat call for heat has cycled since appliance failure occurred WARNING Electrical Shock Hazard Can cause severe injury death or property damage Only a trained experienced service technician should perform this troubleshooting 1 Make sure th...

Page 12: ...e If you do not smell gas continue with the next step 6 Move the ignition system control switch to the ON position 7 Replace the ignition system control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on move the ignition system control switch to the OFF position and contact a qualified service technician fo...

Page 13: ...H PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE CLOSES YES YES ...

Page 14: ...ll for heat is still present 1 Gas supply off or at too low pressure to operate appliance 2 Damaged or broken HSI element 3 Line voltage HOT leadwire not connected to L terminal on ST9160 or Terminal Board 4 Appliance not properly earth grounded 5 Flame sense rod contaminated or in incorrect location 6 HSI element located in incorrect position 7 Hot surface element or flame sense rod wiring in goo...

Page 15: ...e air intake or exhaust flue system that prevent proper combustion air flow Prepurge time has expired HSI element does not glow red within 10 to 15 seconds 1 Broken or damaged HSI element 2 Broken or damaged HSI element leadwires 3 SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 failure to power HSI element HSI element is glowing red No other visible control system action Wait for HSI element warmup tim...

Page 16: ...pplication Universal Service Part Gas Type Opening Characteristics Ambient Temperatur e Range Includes Replaces Natural to LP Conversion Kit 3 4 in x 1 2 in Reducer Bushings Extension Harness Direct Ignition SV950M2511 Natural Standard Opening 40 F to 175 F 40 C to 79 C Yes None No SV9510M2347 SV9510M2362 SV9410M2902 SV9510M2412 SV9510M2354 SV9410M2910 SV9510M2388 SV9510M2420 SV9520M2536 SV9420M23...

Reviews: