4.2.3 Cable and fuse specifications
Use cables with heat resistance of at least 158°F (+70°C). The cables and the fuses
must be dimensioned according to the tables below. Installation of cables according
to UL regulations is presented in Chapter 4.2.6.
The fuses function also as cable overload protection.
These instructions apply only to cases with one motor and one cable connection from
the frequency converter to the motor. In any other case, ask the factory for more in-
formation.
EMC class
Level H
Level L
Level N
Mains cable types
1
1
1
Motor cable types
3
2
1
Control cable types
4
4
4
Table 4.4 : Cable types required to meet standards. EMC levels are described in
Chapter 4.1.3
Cable type
Description
1
Power cable intended for fixed installation and the specific
mains voltage. Shielded cable not required.
(NKCABLES/MCMK or similar recommended)
2
Power cable equipped with concentric protection wire and
intended for the specific mains voltage.
(NKCABLES /MCMK or similar recommended).
3
Power cable equipped with compact low-impedance shield and
intended for the specific mains voltage.
(NKCABLES /MCCMK, SAB/ÖZCUY-J or similar recom-
mended).
*360º grounding of both motor and FC connection required to meet
the standard
4
Screened cable equipped with compact low-impedance shield
(NKCABLES /Jamak, SAB/ÖZCuY-O or similar).
Table 4.5 : Cable type descriptions
Frame
Type
I
N
[A]
Fuse
[A]
Mains
cable
Cu [AWG]
Terminal cable size (min/max)
Main
terminal
[AWG]
Ground
terminal
[AWG]
Control
terminal
[AWG]
Relay
terminal
[AWG]
MI1
P25 - P75 1,7-3,7
10
2*15+15
15-11
15-11
20-15
20-15
MI2
1P1 - 1P5 4,8-7,0
20
2*13+13
15-11
15-11
20-15
20-15
MI3
2P2
11
32
2*9+9
15-9
15-9
20-15
20-15
Table 4.6 : Cable and fuse sizes for SmartVFD COMPACT, 208 - 240V