9.1 QUICK SETUP PARAMETERS (VIRTUAL MENU, SHOWS WHEN
PAR.13.1 = 1)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1
Motor nominal
voltage
180
690
V
230
400
600
110
Check rating plate on
the motor
P1.2
Motor nominal
frequency
30
320
Hz
50,00
111
Check rating plate on
the motor
P1.3
Motor nominal
speed
300
20000
rpm
1440
112
Default applies for a 4-
pole motor.
P1.4
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on
the motor
P1.5
Motor cos
0,30
1,00
0,85
120
Check rating plate on
the motor
P1.7
0,2 x
I
Nunit
2 x
I
Nunit
A
1,5 x
I
Nunit
107
P1.15
0
1
0
109
0
= Not used
1
= Used
P2.1
1
2
1
172
1
= I/O terminal
2
= Fieldbus
P2.2
0
1
0
505
0
= Ramp
1
= Flying start
P2.3
0
1
0
506
0
= Coasting
1
= Ramp
P3.1
Min frequency
0,00
P3.2
Hz
0,00
101
P3.2
Max frequency
P3.1
320
Hz
50,00
102
P3.3
0
4
3
117
0
= Preset Speeds (0-7)
1
= Keypad Reference
2
= Fieldbus Reference
3
= AI1
(API FULL &
LIMITED)
4
= AI2
(API FULL)
P3.4
0,00
P3.2
Hz
5,00
124
Activated by digital
inputs
P3.5
0,00
P3.2
Hz
10,00
105
Activated by digital
inputs
P3.6
0,00
P3.2
Hz
15,00
106
Activated by digital
inputs
P3.7
0,00
P3.2
Hz
20,00
126
Activated by digital
inputs
Table 9.1: Quick setup parameters