Parameters
Honeywell
9
9.2 MOTOR SETTINGS (CONTROL PANEL: MENU PAR -> P1)
P4.2
Acceleration
time
0,1
3000
s
1,0
103
Acceleration time from 0
Hz to maximum fre-
quency
P4.3
Deceleration
time
0,1
3000
s
1,0
104
Deceleration time from
maximum frequency to
0 Hz.
P6.1
AI1 Signal
range
0
3
0
379
API FULL and LIM-
ITED:
0
= Voltage 0…10 V
1
= Voltage 2…10 V
API LIMITED ONLY:
2
= Current 0…20 mA
3
= Current 4…20 mA
NOTE:
When using API
LIMITED, select the
voltage/current range
also with the dip switch
P6.5
AI2 Signal
range
(API Full only)
2
3
3
390
2
= Current 0…20 mA
3
= Current 4…20 mA
P10.4 Fault autoreset
0
1
0
731
0
= Not used
1
= Used
P13.1
Parameter
conceal
0
1
1
115
0
= All parameters visi-
ble
1
= Only quick setup
parameter group visible
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.1
Motor nominal
voltage
180
690
V
230
400
600
110
Check rating plate on
the motor
P1.2
Motor nominal
frequency
30
320
Hz
50,00
111
Check rating plate on
the motor
P1.3
Motor nominal
speed
300
20000
rpm
1440
112
Default applies for a 4-
pole motor.
P1.4
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on
the motor
P1.5
Motor cos
0,30
1,00
0,85
120
Check rating plate on
the motor
P1.7
0,2 x
I
Nunit
2 x
I
Nunit
A
1,5 x
I
Nunit
107
Table 9.2: Motor settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
Table 9.1: Quick setup parameters