52
Parameters
Honeywell
9
9.10 AUTORESTART PARAMETERS (CONTROL PANEL: MENU PAR ->
P10)
NOTE!
These parameters are shown, when
P13.1 = 0.
9.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
.
Code
Parameter
Min
Max
Unit Default
ID
Note
P10.1
Wait time
0,10
10,00
s
0,50
717
Delay before automatic
restart after a fault has
disappeared
P10.2
0,00
90,00
(FULL &
LIMITED)
60,00
(RS485)
s
30,00
718
Defines the time before
the frequency converter
tries to automatically
restart the motor after the
fault has disappeared
P10.3
Start function
0
2
0
719
0
= Ramp
1
= Flying start
2
= According to P4.2
Affects only to start
after autoreset!
P10.4
Fault autoreset
0
1
0
731
0
= Disabled
1
= Enabled
Table 9.10: Fault autoreset parameters
Code
Parameter
Min
Max
Unit Default
ID
Note
P12.1
0
2
0
163
0
= Not used
1
= PI for motor control
2
= PI for external use
(Only in API FULL)
P12.2 PI controller gain
0,0
1000
%
100,0
118
P12.3
0,00 320,0
s
10,00
119
P12.4
Keypad PI refer-
ence
0,0
100,0
%
0,0
167
P12.5
Setpoint source
0
3
0
332
0
= Keypad PI reference,
P12.4
1
= Fieldbus
2
= AI1
Only in API FULL
& LIMITED
3
= AI2
Only in API FULL
Table 9.11: PI control parameters