Table 6. WEB-RL6N Room Controllers: Overview of terminals and functions (by model)
term.
printing
function
WEB-RL6N
1, 2
--
--
--
3, 4
24V~, 24V0
Removable 24 VAC power supply input
X
5, 6
24V~, 24V0
Aux. output voltage (24 VAC) for all triacs
X
7
TN
Aux. terminal for triac neutral wiring (internally connected with terminals 10 and 13)
X
8
T~
Triac input voltage (24 VAC) for all triacs; triac-switched
X
9
T01
Triac-switched output
X
10
TN
Aux. terminal for triac neutral wiring (internally connected with terminals 7 and 13)
X
11
T02
Triac-switched output
X
12
T03
Triac-switched output
X
13
TN
Aux. terminal for triac neutral wiring (internally connected with terminals 7 and 10)
X
14
T04
Triac-switched output
X
15
--
Not used
--
16, 17
RO4, IN4
Output of Relay 4, Input for Relay 4
type 2
18
RN
Aux. terminal for relay neutral wiring
X
19
RN
Aux. terminal for relay neutral wiring
X
20, 21
IN1, RO1
Input for Relay 1, Output of Relay 1
type 2
22, 23
IN2, RO2
Input for Relay 2, Output of Relay 2
type 1
24, 25
IN3, RO3
Input for Relay 3, Output of Relay 3
type 1
26, 27, 28,
29
C2+, C2-, 24V0, 24V~
RS485 Modbus interface, corr. GND, + aux. power (24 VAC
20%, 50/60 Hz)
X
30, 31
WM1, WM2
Removable interface for Sylk Bus
X
32
AO1
Analog Output 1
type 3
33
GND
Ground for AOs
X
34
AO2
Analog Output 2
type 3
35
24V~
24 VAC power for field devices
X
36
AO3
Analog Output 3
type 1
37
GND
Ground for AOs
X
38
AO4
Analog Output 4
type 1
39
24V~
24 VAC power for field devices
X
40
AO5
Analog Output 5
type 1
41
GND
Ground for AOs
X
42
AO6
Analog Output 6
type 1
43
24V~
24 VAC power for field devices
X
44
24V~
24 VAC power for field devices
--
45
LED
Output to LED of CLCMx
--
46
GND
Ground for UIs
X
47
UI1
Universal Input 1
type 1
48
UI2
Universal Input 2
type 1
49
GND
Ground for UIs
X
50
UI3
Universal Input 3
type 1
51
UI4
Universal Input 4
type 1
52
GND
Ground for UIs
X
53
UI5
Universal Input 5
type 1
54
UI6
Universal Input 6
type 1
55
GND
Ground for UIs
X
56
UI7
Universal Input 7
type 2
57
UI8
Universal Input 8
type 2
58
GND
Ground for UIs
X
59
UI9
Universal Input 9
type 2
60
UI10
Universal Input 10
type 2
61
GND
Ground for UIs
X
62, 63, 64
C1+, C1-, GND
Removable BACnet MS/TP interface and corresponding GND
X
Relay output types Table 3: See. Universal input types: Table 4. Analog output types: See Table 5.