SPYDER MODEL 5 ENGINEERING TOOL
–
USER GUIDE
83
31-00282ES-01
RESULT: The changes are written to the controller. The applications are synchronized. The successful action is displayed
via IRM
Operations Monitor
.
Application Download Failure
Due to various reasons the download of an application can fail. This is shown via message in the
Jobs Sidebar
. In case of
a failed application download, however parts of the application may have already been downloaded to the controller, and
such application parts could start and operate the Spyder Model 5 controller. In this case, damage of the controlled
equipment may occur.
IMPORTANT!
To avoid damaging the controlled equipment or environment due to partial application download failure, it is strongly
recommended to clear the controller and perform the application download again.
Learning from Controller
“
Learn from Controller
”
uploads the current application from the controller in the project. The teaching mode does not
care in this case.
WARNING!
When learning from the controller, the application in the project will be deleted.
If the synchronization status is different, a message displays recommending either to clear the project (modifications are
discarded) or to teach the controller (modifications in the controller are discarded).